DOI QR코드

DOI QR Code

Numerical Analysis of Effects of Water Mist Injection Characteristics on Cooling Performance in Heated Chamber

미분무수 분사 특성에 따른 가열 챔버 내 냉각 성능 수치 해석

  • 수먼 (울산대학교 자동차선박기술대학원) ;
  • 이상욱 (울산대학교 기계공학부)
  • Received : 2012.03.05
  • Accepted : 2012.06.17
  • Published : 2012.06.30

Abstract

Water mist fire suppression systems which use relatively small droplets of water with high injection pressure are increasingly being used in wider applications because of its greater efficiency, low flooding damage and low toxicity. However, the performance of the system significantly relies on the water mist characteristics and it requires better understanding of fire suppression mechanism of water mist. In the present study, computational fluid dynamics simulations were carried out to investigate cooling performance of water mist in heated chamber. The gas phase was prepared with natural convection heat transfer model for incompressible ideal case and then the effects of water mist injection characteristics on cooling capabilities were investigated upon the basis of the pre-determined temperature field. For the simulation of water mist behavior, Lagrangian discrete phase model was employed by using a commercial code, FLUENT. Smaller droplet sizes, greater injection angles and higher flow rates provided relatively higher cooling performance.

Keywords

References

  1. K. C. Adiga, R. F. Hatcher, R. S. Sheinson, F. W. Williams and S. Ayers, "A computational and experimental study of ultra fine water mist as a total flooding agent", Fire Safety Journal, Vol. 42, 2007, pp. 150-160. https://doi.org/10.1016/j.firesaf.2006.08.010
  2. Y. Sinai, P. Stopford, M. Edwards and S. Watkins, "CFD modeling of fire suppression by water spray: sensitivity and validation for a pool fire in a room", The 8th International IBPSA Conference, Netherlands, 2003.
  3. W. Kalata, K. Brown and R. J. Schick, "Dimensional, thermal and evaporative spray plume characteristics using computational fluid dynamics", The 11th Triennial International annual conference and liquid atomization and spray systems, U.S.A, 2009.
  4. M. St-georage and J. M. Bucklin, "Detailed single spray experimental measurements and one dimensional modeling", International Multiphase Flow Journal, Vol. 20, 1994, pp. 979-992. https://doi.org/10.1016/0301-9322(94)90049-3
  5. K. Y. Bae, H. T. Chung, H. B. Kim and Y. S. Han, "Numerical investigation on the effects of water mist characteristics on fire suppression", 2007 Fall KSME Conference, Korea, 2007.
  6. S. E. Gant, "CFD modeling of water spray barriers", Health and safety laboratory report, 2006.
  7. H. T. Chung, C. H. Lee, B. I. Choi, Y. S. Han, and Y. W. Ock, "Application of CFD technigue to performance prediction of spray characteristics of water-mist fire suppression nozzles", Journal of Computational Fluids Engineering, Vol. 11, 2006, pp. 56-61.
  8. A. B. Liu, D. Mather and R. D. Reitz, "Modeling the Effects of Drop Drag and Breakup on Fuel Sprays", SAE Technical Paper 930072, SAE, 1993.
  9. FLUENT Inc., "ANSYS FLUENT 12.0 Theory Guide", Fluent Inc. Lebanon., 2009.
  10. 이창효, 정희택, 최병일, 한용식, 옥영욱, "미분무수 소화시스템의 분무 및 소화 특성 예측을 위한 유동장 수치 시뮬레이션", 대한기계학회 2006년도 춘계학술 대회 논문집, 2006, pp. 710-715
  11. 배강열, 정희택, 김형범, 김찬희, 이창효, 김창, "이동 식 미분무수 노즐의 소화 특성에 대한 수치 시뮬레이션", 한국동력기계공학회 2007년도 춘게학술대회 논문집, 2007, pp. 44-50.