DOI QR코드

DOI QR Code

Modelling of Secondary Arc Using EMTP-RV

EMTP-RV를 이용한 2차 아크 모델링

  • 오윤식 (성균관대학교 정보통신공학부) ;
  • 강성범 (성균관대학교 정보통신공학부) ;
  • 서훈철 (성균관대학교 정보통신공학부) ;
  • 김철환 (성균관대학교 정보통신공학부)
  • Received : 2011.12.30
  • Accepted : 2012.04.25
  • Published : 2012.07.01

Abstract

Most of faults occurred in transmission lines are single-phase to ground faults and transient faults. Single-phase auto reclosing is an appropriate scheme to maintain the system stability and restore the system effectively when those faults are occurred. In single-phase auto reclosing scheme, the secondary arc is generated after faulted phase is tripped to eliminate the fault and it is sustained by the capacitive and inductive coupling to the healthy phases. It is important to reclose the faulted phase after fully extinction of secondary arc because of the damage applied to system. Therefore, it is necessary to research on the detection of secondary arc extinction to ensure high success rate of reclosing. In this step, firstly, the accurate modelling of secondary arc should be performed. In this paper, the modelling of secondary arc is performed by using EMTP-RV and the simulation results show that the implemented model is correct and effective.

Keywords

References

  1. IEEE Power System Relaying Committee Working Group, "Single phase tripping and auto reclosing of transmission lines IEEE committee report", "IEEE Trans. Power Del., vol. 7, no. 1, pp. 182-192, Jan. 1992. https://doi.org/10.1109/61.108906
  2. S.P. Ahn, C.H. Kim, R. K. Aggarwal. and A. T. Johns, "An alternative approach to adaptive single pole auto-reclosing in high voltage transmission systems based on variable dead time control," IEEE Trans. Power Del., vol. 16, no. 4, pp. 676-686, Oct. 2001 https://doi.org/10.1109/61.956756
  3. Wang. Z.J., Yin. Z.D., Wang. M.M., "Influence of Coordinate Controllable Neutral Reactors on UHV Secondary Arc Current", International Conference on Energy and Environment Technology, Vol. 2, pp. 156-159, Oct. 2009.
  4. M. I. Khoroshev, V. Faybisovich. "Analysis of adaptive single phase auto-reclosing for high voltage transmission lines with various compensation levels[C]", IEEE/PES Power Systems Conference and Exposition, 2004, pp. 598-602.
  5. M. Ramold, G. Idarraga, J. Jager. "Transient shunt reactor dimensioning for bulk power transmission systems during normal and faulty network conditions[C]", International Conference on Power System Technology, 2006, pp. 1-6.
  6. M. Kizilcay, G.Ban, L. Prikler, "Interaction of the Secondary Arc with the Transmission System during Single-Phase Autoreclosure", Power Tech Conference Proceedings, 2003 IEEE Bologna, 7 pp. Vol. 2.
  7. L. Prinler, M. Kizilcay, G. Ban, P. Handl, "Improved secondary arc models based on identification of arc parameters from staged fault test records", presented at the 14th Power System Computation Conf., Sevilla, Spain, June 2002.
  8. M. Kizilcay, T. Pniok, "Digital Simulation of Fault Arcs in Power Systems", EMEP Journal, vol., 1, no. 1, pp. 55-60, 1991.
  9. S. Goldberg, William F. Horton, D. Tziouvaras, "A Computer Model of the Secondary Arc in single phase operation of Transmission Lines", IEEE Transaction on Power Delivery, Vol. 4, No. 1, pp. 586-594, Jan. 1989. https://doi.org/10.1109/59.193833