DOI QR코드

DOI QR Code

Analysis of the Harmonics on the Power Line in the Computer Room

전산실에서의 고조파 분석

  • Roh, Deok-Nam (Department of Electrical Engineering, Honam University) ;
  • Eo, Ik-Soo (Department of Electrical Engineering, Honam University)
  • 노덕남 (호남대학교 전기공학과) ;
  • 어익수 (호남대학교 전기공학과)
  • Received : 2012.06.25
  • Accepted : 2012.12.06
  • Published : 2012.12.31

Abstract

This paper deals with the Harmonics on the power lines in the computer room. The voltage and current at each phase of electric power from UPS to the load must be ensured less than 5% distortion rates according to the regulation terms from KEPC(Korea Electric Power Corporation) and the KSC4310 Uninterruptible Power Supply regulation. However, measurements show that the voltage distortion rate conforms those regulations but the current distortion rate exceeds much the limit. This current distortion is stabilized from 34.98% to 15.22% nearly half by an AC current filter.

본 논문에서는 전산실 파워라인의 고조파 문제를 다룬다. 전산실 UPS의 부하 측 각 상의 전압 및 전류는 한국전력공사 전기공급 약관의 규제치 전압 왜형률 5%와 전류 왜형률 5%, 그리고 KS C 4310 의 무정전 전원장치인 UPS의 출력측 고조파 전류 한도 5% 이하를 만족시켜야 한다. 그러나 측정 결과 전압 왜형률은 0.86%로 한국전력공사 규제치에 부합하나, 전류 왜형률은 34.98%로 한국전력공사 규제치인 5%를 초과하여 부적합하였다. 이에 대한 대책으로 AC필터를 설치한 결과 전류 왜형률이 15.22%로, 기준 값 이내에는 미치지 못하였으나 본래의 34.98%에서 절반에 가까운 수준에는 근접 하는 효과가 있었다.

Keywords

References

  1. Roh DeokNam "Analysis of the Harmonics on the Power Line in the Computer Room" Master Degree Paper Vol. 01, No 1, pp 1-7 December 2012.
  2. Noh Uicheol "LCL Filter Design for Grid-connected PCS Using Total Harmonic Distortion and Ripple Attenuation Factor", Power Electronics Institute, Vol. 3, No. 15, pp. 235-243, Jun 2010. Article(CrossRefLink)
  3. Choe Hyeongbeom "A Study on the Harmonic Characteristics of Typical Household loads by Field Measurements", Illuminating and Electrical Installation Engineers Vol. 4, No. 22, pp. 100-106, Apr 2008.
  4. Lee Eunwoong "Characteristics Analysis of Capacitor and Reactor for Harmonic Filter", Electrical Engineers Vol. 1, No. 58P, pp. 1-8, Mar 2009.
  5. Mun Seungil "A Study on Power Factor Control of Inverter-based DG System with Considering the Capacity of an Active Harmonic Filter and an Inverter", Electrical Engineers Vol. 11, No. 58, pp. 2149-2154, Nov 2009.