Full-Scale Test of Smoke-Control Performance of a Subway Tunnel

지하철 본선터널 제연성능 실물 실험

  • 박원희 (한국철도기술연구원 친환경연구실) ;
  • 이덕희 (한국철도기술연구원 친환경연구실) ;
  • 정우성 (한국철도기술연구원 친환경연구실)
  • Received : 2011.06.08
  • Accepted : 2011.08.12
  • Published : 2011.08.31

Abstract

Hot smoke test is done in a subway tunnel. Alcohol trays of 1.0 MW and smoke generators are used for generating hot smoke. The fans equipped with the tunnel are successively run 9 min after smoke generation. It is verified how hot smoke is controlled by fans. Velocity and direction of flow, temperature and smoke density are measured and analyzed for smoke control performance of the tunnel with fans and analyzed from the fire-safety-point of view. Velocity of smoke flow is obtained by using measured velocity and temperature at the ceiling of the tunnel. The time when smoke-control flow is builded up is different for the different positions. Velocity distributions at various positions will be used for the boundaries and the comparison data in numerical simulations for evaluation on smoke-control facilities of subway tunnel.

지하철 본선터널에서 고온 연기시험을 수행하였다. 고온의 화재연기를 모사하기 위하여 약 1.0MW의 알콜트레이 및 연기발생장치를 이용하였다. 화재발생후 9분 후에 터널내에 설치된 팬이 순차적으로 작동하여 화재 연기가 제어되는지를 확인하였다. 터널내의 주요 위치에서의 풍속, 풍향, 온도 및 연기농도 등을 측정하여 이를 화재안전 관점에서 분석하였다. 화재 인근의 천장부분의 풍속 측정값으로 연기의 속도를 구하였으며, 위치별 제연기류가 형성되는 시간이 상이한 것을 확인하였다. 본 연구에서 계측된 풍속분포를 이용하여 지하철 본선터널 제연설비 성능 평가를 위한 수치해석의 경계값 및 비교결과로 활용될 것이다.

Keywords

References

  1. H. Ingason and Y.Z. Li, "Model Scale Tunnel Fire Tests with Longitudinal Ventilation", Fire Safety Journal, Vol.45, No.6-8, pp.371-384(2010). https://doi.org/10.1016/j.firesaf.2010.07.004
  2. R.O. Carvel, A.N. Beard and P.W. Jowitt, "The Effect of Forced Longitudinal Ventilation on a Pool Fire in a Tunnel", Interflam '99, 8th International Fire Science & Engineering Conference, Edinburgh, Scotland, pp.1267-1272(1999).
  3. R.O. Carvel, A.N Beard and P.W. Jowitt, "The Influence of Longitudinal Ventilation Systems on Fires in Tunnels", Tunnelling and Underground Space Technology, Vol.16, pp.3-21(2001).
  4. D.H. Kim and W.H. Park, "Experiment by Using Reduced Scale Models for the Fire Safety of a Rescue Station in Very Long Tunnel in Korea", Tunnelling and Underground Space Technology, Vol.21, No.3-4, p.303(2006). https://doi.org/10.1016/j.tust.2005.12.159
  5. 국토해양부, "철도시설 안전세부기준"(2008).
  6. 국토해양부, "철도시설 안전세부기준"(2008).
  7. 국토해양부, "도시철도 건설규칙"(2008).
  8. 박원희, 장희철, 김동현, 김태국, "지하철 역사 승강장 화재발생시 열/연기 거동 분석을 위한 실험 및 수치 연구 (I) -실험적 접근-", 한국화재소방학회 논문지, Vol.20, No.3, pp.9-14(2006).
  9. http://www.smokemachines.net/buyvicount compacts.html.
  10. S. Sardqvist, "Initial Fires", Lund University(1993).