DOI QR코드

DOI QR Code

Heating Performance Evaluation of the VRF Heat Pump System with Refrigerant Heating Cycle for the Extreme Cold Region

냉매 가열식 대용량 VRF 히트펌프 사이클 설계를 통한 극한랭지 난방 성능 평가

  • Received : 2011.02.21
  • Published : 2011.08.10

Abstract

Heat pump systems for commercial building with variable refrigerant flow(VRF) are expanding a market due to high energy efficiency, lower maintenance cost and easy installation comparing with the conventional heat pump with the constant refrigerant flow. In general, heat pump systems degrade the energy efficiency in the extremely low temperature regions. In this study, VRF heat pump system with refrigerant heating is experimentally investigated to overcome the low heating performance in the extremely low temperature regions. VRF heat pump system with refrigerant heating is found out the sufficient heating performance in the -25 degree temperature condition comparing with the conventional heat pump system and is obtained more than 2,500 kPa high pressure in the evaporator at low temperature.

Keywords

References

  1. Yoshihazu Nishihara, 2007, The Room Air-conditioner of the nonstop heating with a heater type refrigerative heater, Japanese Journal of Refrigeration, Vol. 82, No. 952, pp. 8-13.
  2. Kim, S. H. and Park, Y. C., 2006, An experimental study on the performance of a heat pump with a refrigerant heating device, Korean Journal of Air conditioning and Refrigeration Engineering, Vol. 18, No. 9, pp. 707-713.
  3. Park, Y. C., Kim, S. H. and Kim, J. Y., 2008, Performance of a refrigerant heating type heat pump by changing of driving devices and heat exchangers, Korean Journal of Air conditioning and Refrigeration Engineering, Vol. 20, No. 1, pp. 49-56.
  4. Yamakasi, K., Okata, A., Maeno, M., and Ito, C., 1998, Development of burner for room air conditioner, Mitsubishi Juko Giho:Air Conditioning and Refrigeration, Vol. 35, No. 2, pp. 96-99.
  5. Ma Guoyuan, Chai Qinhu and Jiang Yi, 2003, Experimental investigation of air-source heat pump for cold regions, International Journal of Refrigeration, Vol. 26, pp. 12-18. https://doi.org/10.1016/S0140-7007(02)00083-X
  6. Lubliner, M., Andrews, J. and Baylon, D., 2005, Heating with residential heat pumps, ASHRAE Journal, Vol. 47, No. 10, pp. 36-40.
  7. Byun, J. S., Lee, J. H. and Jeon, C. D., 2008, Frost retardation of an air-source heat pump by the hot gas bypass method, International Journal of Refrigeration, Vol. 31, pp. 328-334. https://doi.org/10.1016/j.ijrefrig.2007.05.006
  8. KATS, 2010, KS C 9306 Air Conditioner Standard.