DOI QR코드

DOI QR Code

산업용 냉각기의 압축기 회전수 변화에 따른 용량제어 특성

The characteristics of capacity control using a variable speed compressor in an industrial cooler

  • 투고 : 2011.02.22
  • 심사 : 2011.04.06
  • 발행 : 2011.04.30

초록

This paper presents the capacity-control characteristics in an industrial cooler with a variable speed compressor. The inverter-type compressor is controlled by the rotational speed of the operational frequency. This type of the compressor performs the wide range of load compared to the on-off type. When the load of the system reduces, the rotational speed will be reduced. Thus, the system leads to the less power consumption and extends the longer durability of the compressor. With the variable rotational speed of the compressor the cooling capacity of the cooler is about 1.6-3.6 kW and the capacity control is about 40-100%. The system showed the highest efficiency when the rotational speed is about 45-70 Hz. The results can be used as the basic design data to control an industrial cooler.

키워드

참고문헌

  1. S. M. Beak, J. H. Choi, J. Y. Byun, C. G. Moon, H. S. Lee, S. K. Jeong, and J. I. Yoon, 2009, "Characteristics of Temperature Control by Hot-gas Bypass Flow Rate on Industrial Water Cooler", Journal of the Korean Society of Marine Engineering Vol.33, No. 8, pp. 55-62.
  2. J. H. Choi, S. M. Baek, B. J. Jin, W. J. Choi, C. G. Moon, H. S. Lee and J. I. Yoon, 2009, "Performance Characteristics of Cooler Controled Capacity Using Hot-Gas Bypass", ICHMT CONV -09 Tunisia, pp.502-505.
  3. Cohen. R, J. F. Hamilton and J. T. Pearson, 1974 "Possible energy conservation through the use of variable-capacity compressor", Proc. Purdue Compressor Technology Cong., Purdue, USA, pp. 50-54.
  4. Lida. K, T. Yamamoto, T. Kuroda and H. Hibi, 1982, "Development of an energy saving oriented variable-capacity system heat pump", ASHRAE Trans., No. 88, pp. 441-449.
  5. Ischii. N, M. Yamamura, H. Morokiski, M. Fukushima, 1988, "On the superior dynamic behaviour of a variable rotating speed scroll compressor", Proc. Purdue comp. Tech. Conf. Purdue. USA, pp. 7-82.
  6. Ischii. N, M. Yamamura. S. Muramatsy, et al., 1990, "Mechanical efficiency of a variable speed scroll compressor", Proc. Purdue comp. Tech. Conf. Purdue. USA, Vol. 1, pp. 192-199.
  7. S. M. Beak, C. G. Moon, H. W. Kim, S. K. Jeong and J. I. Yoon, 2010, "Characteristics of Capacity Control of Variable Speed Water Cooler with the Electronic Expansion Valve Open/Close Degree", Journal of the Korean Society of Marine Engineering, Vol.34, No. 1, pp.282-288. https://doi.org/10.5916/jkosme.2010.34.2.282
  8. D. S. Yang, G. b. Lee, M. S. Kim and Y. M. Cho, 2004, "A Study on the Capacity Modulation of a Variable Speed Vapor Compression System using Superheat at the Compressor Discharge," Proceedings of the SAREK 2004 Winter Annual Conference, p. 99.
  9. Hua. Li, J. I. Yoon and S. K. Jeong, 2004, "Dynamic Characteristics of Refrigeration System for Control Evaporator Superheat and Compressor Capacity", The Korean Society for Power System Engineering, KSPSE The 2004 Spring Conference, pp. 170-174.
  10. Sun Chul Kim, Dae Sun Hong and Won Jee Chung, 2004, "Temperature Control for an Oil Cooler System Using PID Control with Fuzzy Logic", Transactions of Korean Society of Machine Tool Engineers, Vol.13, No. 4, pp.87-94.

피인용 문헌

  1. A Study on Efficient Capacity Control of a Marine Pump with the Variation of Sea Water Temperature vol.20, pp.6, 2014, https://doi.org/10.7837/kosomes.2014.20.6.788
  2. Effects of seawater flow rate and evaporation temperature on performance of Sherbet type ice making machine vol.297, pp.1757-899X, 2018, https://doi.org/10.1088/1757-899X/297/1/012069
  3. A Study on the Efficiency Characteristics of ESS of Maritime University Training Ship vol.32, pp.6, 2011, https://doi.org/10.13000/jfmse.2020.12.32.6.1401