Abstract
In performing a series of in-situ thermal response tests, the effective thermal conductivities of six vertical closed-loop ground heat exchangers were experimentally evaluated and compared one another, which were constructed in a test bed in Wonju. To compare thermal efficiency of the ground heat exchangers in field, the six boreholes were constructed with different construction conditions: grouting materials (cement vs. bentonite), different additives (silica sand vs. graphite) and the shape of pipe-sections (general U-loop type vs. 3 pipe-type). From the test results, it can be concluded that cement grouting has a higher effective thermal conductivity than bentonite grouting, and the efficiency of graphite better performs than silica sand as a thermally-enhancing addictive. In addition, a new 3 pipe-type heat exchanger provides less thermal interference between the inlet and outlet pipe than the conventional U-loop type heat exchanger, which results in superior thermal performance. Based on the results from the in-situ thermal response tests, a series of economic analyses have been made to show the applicability of the new addictives and 3 pipe-type heat exchanger.
현장 열응답 시험을 통해 지중 유효 열전도도를 산출하여 각 보어홀의 성능을 비교하기 위해 강원도 원주 현장에 6개의 보어홀을 시험 시공하였다. 6개의 보어홀은 그라우트 종류와 첨가재 종류, 지중열교환기 파이프 단면에 따른 영향을 검토하도록 시공되었다. 그라우트 재료는 벤토나이트와 시멘트를 사용하였으며 첨가재는 천연규사와 흑연, 파이프 단면은 기존 U-tube 파이프 단면과 유입과 유출 파이프 사이에 파이프를 추가로 삽입한 새로운 3공형 파이프 단면을 적용하였다. 현장 열응답 시험으로 산정한 지중 유효 열전도도 결과는 시멘트 그라우트로 시공한 보어홀의 경우가 벤토나이트 그라우트로 시공한 경우에 비해 전열 성능이 향상됨을 보였으며 흑연을 추가로 사용한 경우가 천연규사만 사용한 경우보다 높은 효율을 보였다. 또한, 유입과 유출 파이프 사이에 물을 채워 부분적 단열 구간을 형성한 새로운 3공형 파이프 단면의 경우가 기존 U-tube 파이프 단면에 비해 높은 효율을 보였다. 가상 건물에 대한 지중열교환기 설계를 수행하여 지중열교환기 시공비를 비교한 결과, 시멘트 그라우트에 첨가재로 천연규사와 흑연을 함께 사용한 경우가 벤토나이트 그라우트에 첨가재로 천연규사를 사용한 기존의 시공방법 보다 낮은 시공비로 설계가 가능하였다. 마지막으로 본 현장 열응답 시험결과를 바탕으로 일련의 경제성 분석을 통하여 새로이 제시된 첨가제와 3공형 파이프 단면의 적용성을 평가하였다.