DOI QR코드

DOI QR Code

선형회귀법을 이용한 절연유에 용존된 furfural과 CO, CO2 가스 함유량 간의 상관관계 분석

Analysis for Correlation Between Furfural and CO, CO2 Gas Dissolved Inside Insulating Oil using Linear Regression Method

  • 투고 : 2010.04.20
  • 심사 : 2010.05.20
  • 발행 : 2010.06.01

초록

When paper which was applied as insulation in oil-filled transformer was aged by thermal, its electrical, mechanical and chemical characteristics were changed and deteriorated. Therefore operating temperature was more higher, damage of paper was more quicker. Insulating paper which was generally made with cellulose was degraded, polymer of long length chain was decomposed as a monomer and CO, $CO_2$ gas and/or by-product such as furfural was produced from paper at the same time. In according with detection these gas and furfural by dissolved gas analysis(DGA) and high performance liquid chromatography(HPLC), we have investigated effects of CO, $CO_2$ gas and furfural on insulation of paper. Also we have analyzed for correlation between furfural and CO, $CO_2$ gas using linear regression method that was known as useful, credible statistical analysis.

키워드

참고문헌

  1. 권동진, 곽주식, 은종영, 민병문, 유동균, "변압기 절연유 가스분석과 고장원인 검토", 대한전기학회논문지 54C권 8호, pp.343-349, 2005.
  2. 선종호, 김광화, "유중가스분석에 의한 변압기 이상진단법 기술동향", 대한전기학회 신기술동향 제52권 12호, pp.35-41, 2003.
  3. 김재훈, 한상옥, "CO, $CO_{2}$ 가스와 Furan 함유량의 분석을 통한 셀룰로오스 절연지의 열 열화특성", 대한전기학회논문지 58P권 4호, pp.499-504, 2009.
  4. 박현주, "변압기 진단 신뢰도 향상을 위한 유중가스 분석방법 비교 고찰", 2007년도 대한전기학회 하계학술대회 논문집, pp.758-759, 2007.
  5. 김재훈, 한상옥, "전력용 변압기의 열화에 의해 생성된 부산물의 분석", 대한전기학회논문지 56A권 9호, pp.1561-1555, 2007.
  6. 노형진, "Excel 및 SPSS를 활용한 다변량분석 이론과 실제", 형설출판사, 2005.
  7. 선종호, 이상화, 김광화, "CO와 $CO_{2}$ 가스를 이용한 유입식 변압기 절연지의 열화진단에 관한 연구", 전기학회논문지, 53C권 10호, pp.523-529, 2004.
  8. 한국전력, "주변압기 운영기준", 한국전력공사 송변처, 2008.
  9. 한국전기안전공사, "전력용 변압기의 점검기준에 관한 연구", pp.139-145 2000.
  10. 최광범, "절연유중의 수분 및 Fufural 검출을 이용한 유입변압기 상태진단", 전기학회논문지, 54C권 12호, pp.546-552, 2005.