DOI QR코드

DOI QR Code

22.9kV 배전선로 중성선 설치 구조에 따른 유도뢰 차폐효과 분석

Analysis on the Induced Lightning Shielding Effect According to the Neutral Wire Installation Structure of a 22.9kV Distribution Line

  • 투고 : 2010.01.26
  • 심사 : 2010.03.04
  • 발행 : 2010.06.01

초록

The electricity distribution system in Korea is adopting a multi-grounding system. Protection of this distribution system against lightning is performed by installing overhead ground wires over the high voltage wires, and connecting the overhead ground wires to the ground every 200 m. The ground resistance in this system is limited not to exceed $50\Omega$ and overhead ground wire and neutral wire are multiple parallel lines. Although overhead ground wire and neutral wire are installed in different locations on the same pole, this circuit configuration has duplicated functions of providing a return path for unbalanced currents and protecting the distribution system against induced lightning. Therefore, the purpose of this study is to analyze the induced lightning shielding effect according to the neutral wire installation structure of a 22.9kV distribution line in order to present a new 22.9kV distribution line structure model and characteristics. This study calculated induced lightning voltage by performing numerical analysis when an overhead ground wire is present in the multi-grounding type 22.9kV distribution line structure, and calculated the induced lightning shielding effect based on this calculated induced lightning voltage. In addition, this study proposed and analyzed an improved distribution line model allowing the use of both overhead wire and neutral wire to be installed in the current distribution lines. The result of MATLAB simulation using the conditions applied by Yokoyama showed almost no difference between the induced lightning voltage developed in the current line and that developed in the proposed line. This signifies that shielding the induced lightning voltage through overhead wire makes no difference between current and proposed distribution line structures. That is, this study found that the ground resistance of the overhead wire had an effect on the induced lightning voltage, and that the induced lightning shielding effect of overhead wire is small.

키워드

참고문헌

  1. 전력연구원, "절연설계 신뢰도 향상을 위한 뇌격측정 설비구축에 관한 연구", 최종보고서, 2003.
  2. 우정욱, 심응보, "낙뢰측정에 대한 기술동향과 LPATS 데이터에 의한 한반도 낙뢰현황", 조명.전기설비학회지 제17권 제4호, pp.16-23, 2003.
  3. 우정욱 외, "낙뢰측정 네트워크를 위한 감지기 사이트 서베이와 낙뢰감지율 검토", 전기학회논문지 제55C 제11호, pp. 532-537, 2006.
  4. 松山彰, "送電線雷害防止對策", 電氣評論, 1997
  5. 宮崎輝, "配電線の雷害對策", 電氣評論, 2006.
  6. M. Ishii 外, "Multistory Transmission Tower Model for Lightning Lurge Analysis", IEEE Trans. on Power Delivery, Vol. 6, No.3, pp. 1327–1335, 1991. https://doi.org/10.1109/61.85882
  7. S. Yokoyama, "Calculation of lightning-induced voltages on overhead multiconductor systems", IEEE Trans. on Power Apparatus Systems, Vol. PAS-103, No.1, Jan. 1984.
  8. S. Yokoyama, "Analog Simulation of Lightning Induced Voltages and Its Application fir Analysis of Overhead-Ground-Wire Effects", Proc. IEE, Vol. 132, part C, pp. 208-216, 1985
  9. C. F. Wagner and G. D McCann, "Induced Voltage on Transmission Lines", AIEE Trans, Vol. 61, pp.916-930, 1942
  10. S. Rusck, "Induced Lightning Over-voltages on Power -Transmission Lines with Special Reference to the Over-Voltage Protection of Low Voltage Networks", Trans. Royal Institute of Technology, Stockholm, Sweden, 1958.
  11. P. Chowduri, "Voltages Surges Induced on Overhead Lines by Lightning Strokes", Proc. IEE, Vol.116, pp.561-565, 1969
  12. P. Chowduri, "Lightning-Induced Voltages on Multiconductor Overhead Lines", IEEE Transactions on Power Delivery, Vol. 5, No.2, pp.658-667, 1990 https://doi.org/10.1109/61.53068