A Practical Power System Stabilizer Tuning Method and its Verification in Field Test

  • Shin, Jeong-Hoon (Korea Electric Power Company (KEPCO) Research Institute) ;
  • Nam, Su-Chul (Korea Electric Power Company (KEPCO) Research Institute) ;
  • Lee, Jae-Gul (Korea Electric Power Company (KEPCO) Research Institute) ;
  • Baek, Seung-Mook (Korea Electric Power Company (KEPCO) Research Institute) ;
  • Choy, Young-Do (Korea Electric Power Company (KEPCO) Research Institute) ;
  • Kim, Tae-Kyun (Korea Electric Power Company (KEPCO) Research Institute)
  • Received : 2010.03.30
  • Accepted : 2010.05.10
  • Published : 2010.09.01

Abstract

This paper deals with parameter tuning of the Power System Stabilizer (PSS) for 612 MVA thermal power plants in the KEPCO system and its validation in a field test. In this paper, the selection of parameters, such as lead-lag time constants for phase compensation and system gain, is optimized using linear and eigenvalue analyses. This is then verified through the time-domain transient stability analysis. In the next step, the performance of PSS is finally verified by the generator's on-line field test. After the field test, measured and simulated data are also compared to prove the effectiveness of the models used in the simulations.

Keywords

References

  1. F.P. de Mello, C. Concordia, “Concepts of SynchronousMachine Stability as Affected by ExcitationControl”, IEEE Trans. Vol. PAS-87, June 1969,pp.316-329.
  2. Larsen, E.V. and D.A. Swann, “Applying Power SystemStabilizers, Parts I, II, and III”, IEEE Trans., Vol.PAS-100, No. 6, June 1981, pp.3017-3046.
  3. P. Kundur, D.C. Lee, H.M. Zein El-Din, “Power SystemStabilizers for Thermal Units: Analytical Techniquesand On-Site Validation”, IEEE Trans. Vol.PAS-100, No.1, January 1981, pp. 184-198.
  4. F.P. de Mello, L.N. Hannett, J.M. Undrill, “PracticalApproaches to Supplementary Stabilizing from AcceleratingPower”, IEEE, Trans., Vol. PAS-97, September/October 1978, pp. 1515-1522.
  5. P. Kundur, M. Klein, G.J. Rogers, and M.S. Zywno,“Application of Power System Stabilizers for Enhancementof Overall System Stability”, IEEE Trans.,Vol. PWRS-4, May 1989, pp. 614-629.
  6. J.S. Czuba, L.N. Hannett, J.R. Willis, “Implementationof Power System Stabilizer at the LudingtonPumped Storage Plant”, Presented at the IEEE PESsummer meeting, Vancouver, July 1985.
  7. P. Kundur, Power System Stability and Control,McGraw-Hill, 1994.
  8. D.J. Kim, J.H.Shin, “Basic Study for PSS tuning:PART I-Torque Characteristics according to the systemconditions”, KIEE Trans., Vol. 48-9, Sep. 1999.
  9. J.H.Shin, J.G.Lee “A Tuning Method for the PSS of aLarge Thermal Power Plant and its Application toReal Power System: Part I-Selection of parameters byOff-line Simulation”, Journal of KIIEE., Vol. 23, No.12, Dec. 2009.

Cited by

  1. Design and small signal stability enhancement of power system using interval type-2 fuzzy PSS vol.30, pp.1, 2015, https://doi.org/10.3233/IFS-151825
  2. Suppression of power system forced oscillations based on PSS with proportional-resonant controller vol.27, pp.7, 2017, https://doi.org/10.1002/etep.2328
  3. A new LPV modeling approach using PCA-based parameter set mapping to design a PSS vol.8, pp.1, 2017, https://doi.org/10.1016/j.jare.2016.10.006