Abstract

This paper describes the development of a three-phase line-interactive DVR with a new sag detection algorithm. The developed detection algorithm has a hybrid structure composed of an instantaneous detector and RMS-variation detectors. The source voltage passes through the sliding-window DFT and RMS calculator, and the instantaneous sag detector. If an instantaneous sag is detected, the RMS variation detector-1 is selected to calculate the RMS variation. The RMS variation detector-2 is selected when the instantaneous sag occurs under the operation of the RMS variation detector-1. The feasibility of the proposed algorithm is verified through computer simulations and experimental work with a prototype of a line-interactive DVR with a 3kVA rating. The line-interactive DVR with the proposed algorithm can compensate for an input voltage sag or an interruption within a 2ms delay. The developed DVR can effectively compensate for a voltage sag or interruption in sensitive loads, such as computers, communications equipment, and automation equipment.

Keywords

References

  1. N. Woodley, L. Morgan, A. Sundaram, "Experience with an inverter-based dynamic voltage restorer," IEEE Trans. on Power Delivery, Vol.14, No.3, pp.1181-1186, Jul. 1999. https://doi.org/10.1109/61.772390
  2. B. Han, B. Bae, H. Kim, S. Baek, "Combined operation of unified power quality conditioner with distributed generation," IEEE Trans. on Power Delivery, Vol.21, No.1, pp.330-338, Jan. 2006. https://doi.org/10.1109/TPWRD.2005.852843
  3. C. Zhan, V. Ramachandaramurthy, A. Arulampalam, C. Fitzer, S. Kromlidis, M. Bames, N. Jenkins, "Dynamic voltage restorer based on voltagespace vector PWM control," IEEE Trans. on Industry Applications, Vol.37, No.6, pp.1855-1863, Nov./Dec. 2001. https://doi.org/10.1109/28.968201
  4. M. Newman, D. Holmes, J. Nielsen, F. Blaabjerg, "A dynamic voltage restorer with selective harmonic compensation at medium voltage level," IEEE Trans. on Industry Applications, Vol.41, No.6, pp.1744-1753, Nov./Dec. 2005. https://doi.org/10.1109/TIA.2005.858212
  5. A. Florio and A. Mariscotti, "Voltage sag detection based on rectified voltage processing," IEEE Trans. on Power Delivery, Vol.19, No.4, pp. 1962-1967, Oct. 2004. https://doi.org/10.1109/TPWRD.2004.829924
  6. R. Naidoo and P. Pillay, "A new method of voltage sag and swell detection," IEEE Trans. on Power Delivery, Vol.22, No.2, pp. 1056-1063, Apr. 2007. https://doi.org/10.1109/TPWRD.2007.893185
  7. B. Han and B. Bae, "Novel phase-locked loop using adaptive linear combiner," Letter Section of IEEE Trans. on Power Delivery, Vol. 21, No. 1, pp. 513-514, Jan. 2006. https://doi.org/10.1109/TPWRD.2005.860436

Cited by

  1. A Discrete State-Space Control Scheme for Dynamic Voltage Restorers vol.13, pp.3, 2013, https://doi.org/10.6113/JPE.2013.13.3.400