DOI QR코드

DOI QR Code

Characteristics of Transient Grounding Impedances of Counterpoises Relevant to the Injected Point of Impulse Currents

임펄스전류의 인가위치에 따른 매설지선의 과도접지임피던스 특성

  • 이봉 (인하대학교 대학원 전기공학과) ;
  • 정동철 (인하대학교 대학원 전기공학과) ;
  • 김종호 (인하대학교 대학원 전기공학과) ;
  • 유재덕 (인하대학교 대학원 전기공학과) ;
  • 김동규 (인하대학교 대학원 전기공학과) ;
  • 이복희 (인하대학교 IT공대 전기공학부)
  • Received : 2010.01.07
  • Accepted : 2010.02.01
  • Published : 2010.05.31

Abstract

This paper presents the dependances of transient grounding impedances of counterpoises on the soil structures and the injected point of impulse currents. The transient and conventional grounding impedances of the 25 and 50[m] counterpoises buried in the soil with different resistivity were measured and analyzed as a function of the rise time of impulse currents. As a result, the transient grounding impedances give an inductive behavior, and the trend of the conventional grounding impedances is similar to that of the transient grounding impedances. The ground resistance of counterpoises is irrespective to the injected of impulse current, but the transient and conventional grounding impedances in a short time range especially depend on the soil resistivity and position of the injected point of impulse currents.

본 논문은 매설지선의 과도접지임피던스의 임펄스전류의 인가위치와 대지구조에 대한 의존성에 관한것으로 다른 저항률을 가지는 토양에 매설된 길이 25, 50[m]인 매설지선의 과도접지임피던스와 규약접지 임피던스를 임펄스전류의 상승시간에 따라 측정하고 분석하였다. 그 결과, 매설지선의 과도접지임피던스는 유도성을 나타냈으며, 규약접지임피던스는 과도접지임피던스와 비슷한 경향성을 보였다. 매설지선의 접지저항은 임펄스전류의 인가위치에 관계없지만 특히 과도접지임피던스와 규약접지임피던스는 짧은 시간영역에서 임펄스전류의 인가위치와 대지저항률에 의존적이었다.

Keywords

References

  1. N.Fujimoto, E. P. Dick, S. A. Boggs and G. L. Ford, “Transient Ground Potential Rise in Gsd-Insulated Substations-Experimental Studies”, IEEE Trans. on PAS., Vol.PAS-101, No.10, pp.3603-3609, 1982. https://doi.org/10.1109/TPAS.1982.317033
  2. S. Karaki, et al, “Transient Impedance of GIS Grounding Grid”, IEEE Trans., Vol.PD-10, No.2, pp.723-738,1995. https://doi.org/10.1109/61.400859
  3. 이복희, 이수봉, 장근철, “형상이 다른 접지전극에 접속된 심매설 봉상접지전극의 임펄스접지임피던스 특성”, 조명전기설비학회논문지, Vol. 19, No.2, pp.63-69, 2005. https://doi.org/10.5207/JIEIE.2005.19.2.063
  4. S. Visacro, “A didactic general approach of grounding behavior for lightning currents”, Proc. the 27th ICLP, Avignon, France, Vol. 1, pp. 508-513, 2004.
  5. 이복희: 접지의 핵심 기초 기술, 도서출판 의제, pp.81-92, 1999.
  6. KS C IEC 62305-1, 피뢰시스템-제1부: 일반원칙, pp.3-20, 2007.
  7. IEEE Std 81.2-1991, “IEEE Guide for Measurement of Impedance and Safety Characteristics of Large, Extended or Interconnected Grounding Systems”, IEEE Inc., pp..1731, 1991.
  8. T. Takahashi, T. Kawase, “Calculation of Earth Resistance for a Deep-driven rod in Multi-layer Earth Structure”, IEEE Trans. on PD, Vol.6, No.2, pp.608-614, 1991. https://doi.org/10.1109/61.131118
  9. B. H. Lee, D. C. Jeong, S. B. Lee and K. C. Chang, “Effective Impulse Impedances of Deeply Driven Grounding Electrodes”, KIEE Int. Trans on EA, Vol.4-C, No.5, pp.207-214, 2004.
  10. B. H. Lee, J. S. Park and S. C. Lee, “Experimental Investigations of Transient Impedances of Some Grounding Systems”, Proc. Korea Joint Syms. ED&HVE, pp.237-240, 1997.