Abstract
This paper presents the dependances of transient grounding impedances of counterpoises on the soil structures and the injected point of impulse currents. The transient and conventional grounding impedances of the 25 and 50[m] counterpoises buried in the soil with different resistivity were measured and analyzed as a function of the rise time of impulse currents. As a result, the transient grounding impedances give an inductive behavior, and the trend of the conventional grounding impedances is similar to that of the transient grounding impedances. The ground resistance of counterpoises is irrespective to the injected of impulse current, but the transient and conventional grounding impedances in a short time range especially depend on the soil resistivity and position of the injected point of impulse currents.
본 논문은 매설지선의 과도접지임피던스의 임펄스전류의 인가위치와 대지구조에 대한 의존성에 관한것으로 다른 저항률을 가지는 토양에 매설된 길이 25, 50[m]인 매설지선의 과도접지임피던스와 규약접지 임피던스를 임펄스전류의 상승시간에 따라 측정하고 분석하였다. 그 결과, 매설지선의 과도접지임피던스는 유도성을 나타냈으며, 규약접지임피던스는 과도접지임피던스와 비슷한 경향성을 보였다. 매설지선의 접지저항은 임펄스전류의 인가위치에 관계없지만 특히 과도접지임피던스와 규약접지임피던스는 짧은 시간영역에서 임펄스전류의 인가위치와 대지저항률에 의존적이었다.