DOI QR코드

DOI QR Code

유효성분 동작형 누전차단기(Igc Free ELB)의 원리 및 동작 특성 해석

Analysis of the Principle and Operation Characteristics of an (Igc-Free ELB) Operated by an Active Component

  • 최충석 (전주대학교 소방안전공학과)
  • 투고 : 2010.07.05
  • 심사 : 2010.08.25
  • 발행 : 2010.12.01

초록

This study compares the criteria of earth leakage breakers (ELB) and analyzes the characteristics of an Igc-free ELB operated by an active component which is not misoperated by capacitive current. Even for the same ELB, the earth leakage current flowing through the human body is estimated to be differ greatly depending on the power source, voltage, location and status of contact, contact time duration, etc. Earth leakage breakers are classified based on the rated voltage, rated sensing current, rated operating time etc. Mounting and demounting of the existing equipment can be performed easily since an $I_{gc}$-free ELB is manufactured with the same structure as a conventional ELB. The rated operating current of a conventional and an $I_{gc}$-free ELB is 30mA, the sensing current is 25mA and the rated non-operating current is 15mA. In the analysis of non-operating current characteristics, the rated non-operating current of 15mA was satisfied up to a 20mA charging current in the conventional ELB, but does not satisfy the rated non-operating current as it operates when the resistive leakage current is lower than 15mA for a charging current exceeding 20mA. Also, the ELB is misoperated without a resistive leakage current when the charging current exceeded 25mA. However, the newly developed $I_{gc}$-free ELB satisfied the rated non-operating current even when the charging current was 60mA. Also, in comparison to the interrupting characteristics, it was confirmed that the charging current satisfying the rated non-operating current of the $I_{gc}$-free ELB was three times higher than that of the conventional ELB.

키워드

참고문헌

  1. 한국산업규격, KS C 4613, 한국표준협회, 2006.
  2. Kurt Nowak, "Zwanzig Jahre FI-Schutzschaltung Chronologie und Entwicklung varianten" pp.7-9, aus de 16/1978.
  3. A.W. Smoot, N. Magan, "Method of Calculating electrical body impedance and equipment for measuring leakage currents", p.298, Underwiters Laboratories, USA, 1985.
  4. Koepfen, "Electrounfälle und ihre $Einflu{\beta} gr\"{o}{\beta}en$ aus medizinischer Sicht", Heft 6. Seite 168 bis 173, $M\"{a}rz$. 1966.
  5. Walter F.Hart, P.E., "A Five-part Resistor-Capacitor Network for measurement of Voltage and Current Levels Related to Electric Shock and Burns", pp.183-190, Electrical Shock Safety Criteria, 1985.
  6. W. Holzmann, "Magnetische Werkstoffe $f\"{u}r$ Summenstrom und $Ausl\"{o}ser$ in Fehlerstroms Schutzichalten", pp.2-3, VACUMSCHME, Hanau, 1976.
  7. 최충석 외 5, "전기화재공학", 도서출판 동화기술, pp. 189-198, 202, 2004.
  8. 최충석 외 2, "과전류에 의해 용단된 소선의 특성 해석에 관한 연구", 한국산업안전학회 논문지, Vol.19, No.1, pp.60-65, 2004.3.
  9. 최충석 외 2, "VCTFK의 반복피로에 의한 소손 패턴의 특성 해석", 한국안전학회 논문지, Vol.19 No.4, pp.42-47, 2004.12.
  10. 이재복, 명성호, 조연규, 장석훈, 김점식, "누전차단기 의 뇌써지 동작특성 분석 및 오동작 대책", 대한전기학회 논문지, Vol. 51C, No. 10, pp.479-484, 2007.
  11. 함승진, 한송엽, 고창섭, "새로운 저항성 누전전류 측 정 방법", 대한전기학회 논문지, Vol. 56, No. 8, pp.1397-1404, 2007. 08.
  12. 최충석, 한송엽, "전기설비의 저항성 누설전류 검출 및 특성 해석에 관한 연구", KIEE 전기설비전문위원회 추계학술대회, pp.301-304, 2008. 09.