Analysis on Induced Lightning of a 22.9kV-Y Distribution Line Using a Reduced Model

축소모델을 이용한 22.9kV-Y 배전선로의 유도뢰 분석

  • Received : 2010.10.01
  • Accepted : 2010.11.04
  • Published : 2010.12.01

Abstract

This study fabricated a simulation facility which reduced the structure of a current distribution line to 50:1 in order to analyze the induced lightning shielding effect of a 22.9kV-Y distribution line according to ground resistance capacity, grounding locations, etc. When installing an overhead ground wire, the standard for grounding a distribution line with a current of 22.9kV-Y requires that ground resistance in common use with the neutral line be maintained less than $50\Omega$every 200m span. The reduced line for simulation had 7 electric poles and induced lightning was applied to the ground plane 2m apart from the line in a direction perpendicular to it using an impulse generator. If induced voltage occurred in the line and induced current flowed through the line due to the applied current, the induced voltage and current of the 'A' phase were measured respectively using an oscilloscope. When all 7 electric poles were grounded with a ground resistance of less than $50\Omega$ respectively, the combined resistance of the line was $7.4\Omega$. When an average current of 230A was applied, the average induced voltage and current measured were 1,052V and 13.8A, respectively. Under the same conditions, when the number of grounding locations was reduced, the combined resistance as well as induced voltage and current showed a tendency to increase. When all 7 electric poles were grounded with a ground resistance of less than $100\Omega$, the combined resistance of the line was $14.9\Omega$. When an average current of 236A was applied, the average induced voltage and current of the 'A' phase calculated were 1,068V and 15.6A, respectively. That is, in this case, only the combined resistance was greater than when all 7 electrical poles were grounded, and the induced voltage and current were reduced. Therefore, it is thought that even though ground resistance is slightly higher under a construction environment with the same conditions, it is advantageous to ground all electric poles to ensure system safety.

Keywords

References

  1. 우정욱 외 1명, "낙뢰측정에 대한 기술동향과 LPATS 데이터에 의한 한반도 낙뢰현황", 한국조명전기설비학회 논문지 제17권 제4호, pp.16-23, 2003.
  2. IEEE Std 142-2007, "IEEE Recommended Practice for Electric Power Distribution for Industrial Plants", pp.145-167, 2007.
  3. 전력연구원, "절연설계 신뢰도 향상을 위한 뇌격측정 설 비구축에 관한 연구", 최종보고서, pp.21-22, 2005.
  4. 김경철 외 2명, "배전계통에서 낙뢰보호용 피뢰기의 접 지저항 연구에 관한 연구", 한국조명전기설비학회 논문지 제24권 제6호, pp.107-114, 2010.
  5. Xie Bo et al, "Identification of induced lightning and direct striking based on wavelet transform", IEEE APEMC, pp.1566-1569, 2010.
  6. Wyatt, "An Improved Model for EMP-Induced Lightning", Harry Dimond Labs Adelphi MD Technical Report, 1980.
  7. Abdenbi Mimouni 외 2명, "Lightning–Induced Over Voltages on Overhead Lines: Modelling and Experimental Validation", Journal of Electrical Engineering, Vol.58, No.3, pp.146–151, 2007.
  8. 김점식 외 2명, "22.9㎸ 배전선로 중성선 설치 구조에 따른 유도뢰 차폐효과 분석", 대한전기학회 논문지 59P권 제2호, pp.191-196, 2010.
  9. 한전 배전처, "배전선비 시공실무", pp.52, 205, 2003.
  10. Alexandre Piantini 외 4명, "A Scale Model for the Study of the LEMP Response of Complex Power Distribution Networks", IEEE Trans. on Power Delivery, Vol.22, No.1, pp.710-720, 2007. https://doi.org/10.1109/TPWRD.2006.881410
  11. C. A. Nucci, "Lightning-Induced Voltages on Distribution Systems : Influence of Ground Resistivity and System Topology", Journal of Lightning Research, Vol.1, pp.148-157, 2007.