Measurement Technology of the Dissolved Hydrogen Gas Due to Partial Discharge in Oil using Gas Sensor

가스센서를 이용한 부분방전특성에 따른 유중수소가스 측정연구

  • Published : 2009.09.01

Abstract

This paper describes the measurement technology of the dissolved hydrogen gas due to partial discharge in oil using gas sensor. For higher resolution and less error in measurement of the dissolved hydrogen gas in oil, the sensor outputs with ambient temperature which affect the sensor output characteristics should be considered. The sensor output trends with ambient temperature and the properties of the dissolved hydrogen gas in oil with partial discharge characteristic were analyzed through the test results. It was indicated that the sensor peak and the base voltage with measuring time were affected by ambient temperature and the measurement errors of the sensor output by temperature were reduced by using the difference between the peak and the base voltage rather than just the peak voltage. In addition, the hydrogen gas sensor outputs were increased with the increase of partial discharge energy.

Keywords

References

  1. Y. Inoue et aI., 'Development of oil dissolved hydrogen gas detector for diagnosis of transformers', IEEE Trans. on Power Delivery, Vol. 5, No.1, January 1990, pp. 232-236 https://doi.org/10.1109/61.107277
  2. Shigemitsu Okabe, Takashi Hara., 'Study on Early Detection of Incipient Faults in Oil Filled Transformes by Analysis of Dissolved Gas in Oil', T. IEE Japan. Vol.116-13. No.9(1996)
  3. Hiroshi Kuwahara, Keiji Tsuruta : 日本電氣學會論文誌 A 97券5号, p267(昭 52-5) - シリコーソ油中の放電に よる ガスの 發生
  4. IEEE Std C57.104-1991, IEEE Guide for the interpretation of Gases Generation in Oil-Immersed Transformers
  5. C. Weigen et.al., 'Study on Intelligent Sensor Used in Transformer On Line Monitoring', Proceedings of 12th AECD, November 2004
  6. Joseph J. kelly, 'Transformer fault diagnosis by dissolved gas analysis', IEEE Trans. on Industry Applications, Vol 16, No.6, 11-12 1980, pp. 777-782 https://doi.org/10.1109/TIA.1980.4503871
  7. 선종호 외, '지능형 유중가스 분석기술기반 유입식변압기 전산관리 프로그램 개발', Trans. KIEE Vol. 54C, No. 12, Dec. 2005
  8. R. Qin, 'An Oil/Gas Separation Membrane and Its Use in Gas Sensor for On Line Incipient Fault Monitoring of Transformer, Proceedings of the 12th ACED, November 2004
  9. Xiao Dengming et. aI., 'New Apparatus for Detecting Transformer Faults Online', Proceedings of The 6th ICPADM, June 21-26, 2000
  10. A. Varl, 'On-Line Diagnostics of Oil Filled Transformers', Proceedings of ICDL-2002, July 7-12, 2002
  11. 허종철 외, '가스수집시간을 이용한 유중수소가스 측정감도향상연구', 대한전기학회 논문지, 제 58권, 제3호, 2009. 03
  12. Takayuki. K, Shigeyuki.T Yoshihara. O, 'Improvement in Diagnostic Method for Transformer based on Dissolved Gas Analysis' 日本電氣學會 電力, ェネルギ 部門大會
  13. Takashi Ishi, Yoshihiro Makino, 'A New Technique or Diagnosis of the Oil Filled Transformer Based on Dissolved Gas Analysis,' 日本電氣學會 SA-00-45 (平12年11月)
  14. 가스센서와 그응용(1999), 김영해 저[기전연구사] pp.65-66
  15. 'IEC 60270(2000), High voltage test techniques - Partial discharge measurement