Evaluation of Errors Due to Earth Mutual Resistance in Measuring Ground Impedance of Vertically-driven Ground Electrode

수직 접지전극의 접지임피던스 측정에서 도전유도에 의한 오차 평가

  • 최종혁 (인하대 IT공대 전기공학과) ;
  • 최영철 (인하대 IT공대 전기공학과) ;
  • 이복희 (인하대 IT공대 전기공학과)
  • Published : 2009.09.01

Abstract

Ground impedance for the large grounding system is measured according to the IEEE Standard 81.2 which is based on the revised fall-of-potential method of installing auxiliary electrode at a right angle. When the auxiliary electrodes are located at an angle of $90^{\circ}$, the ground impedance inevitably includes the error due to earth mutual resistance. In this paper, in order to accurately measure the ground impedance of vertically-driven ground electrodes, error rates due to earth mutual resistance are evaluated by ground resistance and ground impedance measuring devices and compared with calculated values. As a result, the measured results are in good agreement with the computed results considering soil layer with different resistivity. The error rates due to earth mutual resistance decrease with increasing the length of ground electrode in the case that the ratio of the distance between the ground rod to be measured and the auxiliary electrodes to the length of ground electrode(D/L) is same. The ground impedance should be measured at the minimum distance between the auxiliary electrodes that will have an estimated measurement accuracy due to earth mutual resistance.

Keywords

References

  1. IEEE std. 81, IEEE Guide for Measuring Ground Resistivity, Ground Impedance, Ground Surface Potentials of a Ground System, pp.19-24, 1983
  2. F. Dawalibi and D. Mukhedkar, 'Ground electrode resistance measurement in non-uniform soils', IEEE Trans. Vol. PAS-93, No.1, pp.109-116, 1974 https://doi.org/10.1109/TPAS.1974.293921
  3. F. Dawalibi, D. Mukhedkar, 'Resistance measurement of large grounding systems', IEEE Trans. Vol. PAS-98, No. 6, pp.109-116, 1974 https://doi.org/10.1109/TPAS.1979.319434
  4. IEEE Std. 81.2, IEEE Guide for Measurement of Impedance and Safety Characteristics of Large, Extended or Interconnected Grounding Systems, pp.12-17, 1991
  5. J. Ma and F. Dawalibi, 'Extended analysis of ground impedance measurement using the fall-of potential method', IEEE Trans. on PD, Vol.17, No.4, pp.881-885, 2002 https://doi.org/10.1109/TPWRD.2002.803738
  6. 이복희, 이승철, '접지의 핵심 기초 기술', 도서출판 의제, pp.46-56, pp.73-76, 1999
  7. C. G. Wang, T. Takashima, T. Sakuta, and Y. Tsubota, 'Grounding Resistance Measurement Using Fall-of-Potential Method with Potential Probe Located in Opposite Direction to the Current Probe', IEEE Trans. on PD., Vol.13, No.4, pp.1128-1135, 1998 https://doi.org/10.1109/61.714472