선박용 팬코일장치 냉각관 주위의 유동특성에 관한 연구

A Study on the Flow Characteristics around Cooling Tubes of Fan Coil Unit for Ship

  • 발행 : 2009.06.30

초록

이 연구에서는 선박용 팬일유니트의 엇갈림 냉각관 주위 유동특성을 실험적으로 고찰하였다. 입자영상유속계를 이용하여 입구유속기준 레이놀즈수 Re = $1.5{\times}10^3$에서 Re = $2.5{\times}10^3$까지 계측결과를 얻었다. 그 곁과 유동은 흐름방향으로 빠른 속도로 발달하여 비교적 짧은 거리 후방에 공간적인 주기성을 나타내었다. 유동이 발달하는 영역에서는 레이놀즈수에 의존하는 경향이 크게 나타났으나 공간적 주기성에 미치는 레이놀즈수의 영향은 크지 않았다.

This experimental study investigated in to the flow characteristics around staggered cooling tube arrays of fan coil unit for ship. A particle image velocimetry technique was employed to obtain detailed measurements at inlet-velocity-based Reynolds numbers of $Re=1.5{\times}10^3{\sim}Re=2.5{\times}10^3$. As for the results, the flow evolves rapidly and becomes spatially periodic in the streamwise direction after a relatively short distance. The flow exhibits strong Reynolds number dependence in developing region but no significant Reynolds number effects are observed in spatially periodic region.

키워드

참고문헌

  1. 김경천, 정양범(1991), 원주의 근접후류에 대한 자유흐름 난류강도의 영향, 대한기계학회 논문집, Vol. 15, No. 6, pp. 2062-2072.
  2. 임용섭, 손동기, 이준식, 양경수(1998), Reynolds수와 난류강도의 변화에 따른 실린더주위 유동 박리점의 거동에 관한 실험적 연구, 대한기계희회 논문집, Vol. 22, No. 7, pp. 889-898.
  3. 정기범, 조동우(1999), 인텔리전트빌딩에서 개별공조시스템의 최근 동향, 냉동공학회지, Vol.28, No.3, pp.196-202
  4. 조석호, 부정숙(1989), 일렬관군에서 난류 후류특성에 관한 연구, 대한기계학회 논문집, Vol. 13, No.5, pp. 1023-1031.
  5. 태춘섭(1994), 개별 분산공조시스템의 고찰, 공기조화.냉동공학회지, Vol.23, No.1, pp. 37-52.
  6. 황원택, 김세훈(1995), 공간절약을 위한 천장형 분산 공조기, 냉동공희회지, Vol.24, No.6, pp. 628-634.
  7. Avisar Barak, Lev Shemer and Abraham Kribus(2001), Measurements of velocity fields in finite cylinder arrays with and without tip clearance, Experimental Thermal and Fluid Science, Vol. 24, pp. 157-167. https://doi.org/10.1016/S0894-1777(01)00048-6
  8. Buyruk(2002), E. Numerical study of heat transfer characteristics on tandem cylinders, inline and staggered tube banks in cross-flow of air, International Communications in Heat and Mass Transfer, Vol. 29, pp. 355-366. https://doi.org/10.1016/S0735-1933(02)00325-1
  9. Kim M. H. and Clark W. Bullard(2002), Air-side performance of brazed aluminum heat exchangers under dehumidifying conditions, J. Refrigeration, Vol. 25, pp. 924-934. https://doi.org/10.1016/S0140-7007(01)00106-2
  10. Kim M. H., B. Youn and Clark W. Bullard(2001), Effect of inclination on the air-side performance of a brazed aluminum heat exchanger under dry and wet conditions, J. Heat and Mass Transfer, Vol. 44, pp. 4613-4623. https://doi.org/10.1016/S0017-9310(01)00104-1
  11. Niu J. L., L. Z. Zhang and H. G. Zuo(2002), Energy savings potential of chilled-ceiling combined with desiccant cooling in hot and humid climates, Energy and Buildings, Vol. 34, pp. 487-495. https://doi.org/10.1016/S0378-7788(01)00132-3
  12. Obara H. and Y. Matsudaira(1998), Vortex Generating Process behind a Pair of Circular Cylinder, Proc. of 4th KSME-JSME Fluids Eng. Conf., pp. 141-144.
  13. Scholten J. W. and D. B. Murray(1998), Heat transfer and velocity fluctuations in a staggered tube array, International Journal of Heat and Fluid Flow, Vol. 19, pp. 233-244. https://doi.org/10.1016/S0142-727X(98)00007-1
  14. Tham K. W., S. C. Sekhar and David Cheong(2002), Indoor air quality comparison of two air-conditioned zones served by the same air-handling unit, Building and Environment, Vol. 37, pp. 947-960. https://doi.org/10.1016/S0360-1323(01)00084-1
  15. Williamson C. H. and K. Vortex(1996), Dynamics in the Cylinder Wake, Annu. Rev. Fluid Mech., Vol. 28, pp. 477-539. https://doi.org/10.1146/annurev.fl.28.010196.002401
  16. West G. S. and C. J. Apelt(1982), The Effects of Tunnel Blockage and Aspect Ratio on the Mean Flow Past a Cylinder with Reynolds Numbers Between $10^{4}\;and\;10^{5}$, J. Fluid Mech., Vol. 114, pp. 361-377. https://doi.org/10.1017/S0022112082000202