Abstract
This study presents comparison of heat transfer and air side friction characteristics in a condenser condition of air conditioner between Louver fin-tube heat exchangers and aluminum parallel heat exchangers. All experiments are performed using an air-enthalpy type calorimeter, which is designed based on the method described in ASHRAE standards. The air velocities crossing the heat exchanger tubes are varied from 0.7 to 1.6 m/s with 0.3 m/s interval, maintaining air dry temperature and relative humidity at $20^{\circ}C$ and 60% respectively. Water temperature and flow rate inside the tube are $70^{\circ}C$ and 10 LPM, respectively. Experimental results show that the heat transfer performances of aluminum heat exchangers are 17-163% higher than those of Louver fin-tube heat exchangers based on the data per unit volume, mass, and heat transfer area, whereas air side pressure drops of aluminum heat exchangers are 19-81% lower.
본 논문에서는 루버형 핀 형상을 가진 핀-튜브 열교환기와 알루미늄 평행류 열교환기의 에어컨 응축기 조건에서의 열전달 성능과 공기측 압력강하 특성을 비교하였다. 모든 실험은 ASHRAE 표준에 근거해 제작된 공기엔탈피형 칼로리미터를 사용하여 수행하였다. 관외 측 공기 속도는 0.7-1.6 m/s까지 0.3 m/s 간격으로 변화시켰으며 건구온도는 $20^{\circ}C$, 상대습도는 60%로 유지하였다. 관내 측 물의 입구온도는 $70^{\circ}C$, 유량은 10 LPM로 고정하였다. 알루미늄 열교환기의 열전달 성능은 루버 핀-튜브 열교환기보다 단위체적당, 단위질량당, 단위열전달면적당 약 17-163%정도 높게 나타나는 연구결과를 보였으며 반면에 공기측 압력강하는 핀-튜브 열교환기에 비해 약 19-81% 정도 낮게 나타났다.