Detection Method of Series Arc Signal

직렬아크신호지 검출방법

  • 길경석 (한국해양대학교 전기전자공학부) ;
  • 지홍근 (한국해양대학교 전기전자공학부) ;
  • 박대원 (한국해양대학교 전기전자공학부) ;
  • 김일권 (한국해양대학교 전기전자공학부) ;
  • 류길수 (한국해양대학교 IT공학부) ;
  • 송재용 (국립과학수사연구소)
  • Published : 2008.10.30

Abstract

This paper dealt with a detection method of series arc existence which is a symptom of electric fires in low-voltage system. The proposed detection circuit consists of a high-pass filter with a low cut-off frequency of 3kHz to attenuate power frequency voltage by 80 dB and an active band-pass filter with a center frequency of 4kHz to detect only the series arc signals. The performance of the circuit was evaluated in a phase-controlled incandescent lamp as a non-linear load and an inverted-fed induction motor as a high frequency load by using the arc generator specified in UL1699. From the experimental results, it was confirmed that the proposed method solved the detection error, which is being the most problem, by discriminating the series arc signal even in non-linear and high frequency loads.

본 논문은 저압계통에서 전기화재의 징후인 직렬아크의 검출방법에 대해 기술하였다. 제안한 검출회로는 전원주파수 성분을 80dB 이상 감소시킬 수 있는 저역차단주파수가 3kHz인 고역통과필터와 아크신호만을 검출하기 위한 중심주파수가 4kHz인 대역통과필터로 구성된다. UL1699에 규정된 아크발생장치를 이용하여 비선형부하인 위상제어 백열전구와 고주파발생부하인 인버터 추동 유도전동기에서 직렬아크신호를 모의하여 성능을 평가하였다. 실험 결과로부터 세안한 방식은 비선형부하와 고주파발생하에 대해서도 직렬아크신호를 정확히 구분함으로써 현재 최대 문제인 검출오류를 해결하였음이 확인되었다.

Keywords

References

  1. 소방방재청(2007), "2006년도 화재통계 연감"
  2. George D. Gregory(1998), "The Arc-Fault Circuit Interrupter : An Emerging," IEEE Trans. on Industry Applications, Vol. 34, No. 5, pp.928-933 https://doi.org/10.1109/28.720431
  3. Chunlin Li, Francis Dawson, Hassan Kojori, Chris Meyers, and Edwin Yue (2003), "Arc Fault Detection and Protection - Opportunities and challenges," SAE Technical Papers, pp.590-597
  4. 이상호, 오홍석(2002), "전기화재 예방을 위한 EFPCD 동작 특성에 관한 연구", 한국화재소방학회, Vol. 12, No. 3, pp.8-11
  5. C. S. Maroni, R. Cittadini, Y. Cadoux & M. Serpinet (2001). "Series arc detection in low voltage distribution switchboard using spectral analysis," ISSPA, pp.473-476
  6. Underwriters Laboratories(2006), "UL1699-Standard for Arc-Fault Circuit-Interrupters"
  7. 지홍근, 박찬용, 길경석, 김일권, 조영진(2008), "저압계통에서 직렬아크신호의 검출", 한국철도학회춘계학술대회, pp.104.1-104.5
  8. Carlos E. Restrepo(2007), "Arc Fault Detection and Discrimination Methods," IEEE Conf. on Electrical Contacts, pp.115-122
  9. Robert F. Couhglin, Frederick F. Driscoll(1987), Operational Amplifiers Linear Integrated Circuits 3rd Edition, Prentice-Hall, INC