Performance of Heat Pumps Charged with R170/R290 Mixture

R170/R290 혼합냉매 적용 히트펌프 성능 평가

  • 박기정 (인하대학교 대학원 기계공학과) ;
  • 이철희 (인하대학교 대학원 기계공학과) ;
  • 정동수 (인하대학교 기계공학과)
  • Published : 2008.09.10

Abstract

In this study, performance of R170/R290 mixtures is measured on a heat pump bench tester in an attempt to substitute R22. The bench tester is equipped with a commercial hermetic rotary compressor providing a nominal capacity of 3.5kW. All tests are conducted under the summer cooling and winter heating conditions of $7/45^{\circ}C$ and $-7/41^{\circ}C$ in the evaporator and condenser respectively. During the tests, the composition of R170 is varied from 0 to 10% with an interval of 2%. Test results show that the coefficient of performance (COP) and capacity of R290 are up to 15.4% higher and 7.5% lower than those of R22 for both conditions respectively. For R170/R290 mixture, the COP decreases and the capacity increases with an increase in the amount of R170. The mixture of 4%R170/96%R290 shows the similar capacity and COP as those of R22. For the mixture, the compressor discharge temperature is $16{\sim}30^{\circ}C$ lower than that of R22. There is no problem with mineral oil since the mixture is mainly composed of hydrocarbons. The amount of charge is reduced up to 58% as compared to R22. Overall, R170/R290 mixture is a good long term 'drop-in' candidate to replace R22 in residential air-conditioners and heat pumps.

Keywords

References

  1. Montreal Protocol on Substances That Deplete the Ozone Layer, 1989, Final Act, United Nations Environment Programme
  2. Global Environmental Change Report, 1997, A Brief Analysis of the Kyoto Protocol, Vol. 9, No. 24, December
  3. Chang, Y. S., Kim, M. S. and Ro. S. T., 2000, Performance and heat transfer characteristics of hydrocarbon refrigerants in a heat pump system, Int. J. Refrigeration, Vol. 23, pp. 232-242 https://doi.org/10.1016/S0140-7007(99)00042-0
  4. Fernaldo, P., Palm, B., Lundqvist, P. and Granryd, E., 2004, Propane heat pump with low refrigerant charge : design and laboratory tests, Int. J. Refrigeration, Vol. 27, pp. 761-773 https://doi.org/10.1016/j.ijrefrig.2004.06.012
  5. Purkayastha, B. and Bansal, P. K., 1998, An experimental study on HC290 and a commercial liquefied petroleum gas (LPG) mix as suitable replacements for HCFC22, Int. J. Refrigeration, Vol. 21, pp. 3-17 https://doi.org/10.1016/S0140-7007(97)00083-2
  6. Granryd, E., 2001, Hydrocarbon as refrigerants- an overview, Int. J. Refrigeration, Vol. 24, pp. 15-24 https://doi.org/10.1016/S0140-7007(00)00065-7
  7. Hwang, Y., Jin, D. H. and Radermacher, R., 2007, Comparison of R-290 and two HFC blends for walk-in refrigeration systems, Int. J. Refrigeration, Vol. 30, pp. 633-641 https://doi.org/10.1016/j.ijrefrig.2006.10.007
  8. ANSI/ASHRAE Addenda a, b, c, d, e, f, g, and h to ANSI/ASHRAE Standard 34-2007, 2007, Designation and Safety Classification of Refrigerants, ASHRAE (June)
  9. Kruse, H., 1996, The state of the art of the hydrocarbon technology in household refrigeration, Proc. of the Int. conferences on ozone protection technologies, Washington (DC), pp. 179-188
  10. Jung, D., Kim, C., Song, K. and Park, B., 2000, Testing of propane/isobutane mixture in domestic refrigerators, Int. J. Refrigeration, Vol. 23, pp. 517-527 https://doi.org/10.1016/S0140-7007(99)00084-5
  11. Int. Energy Agency's Heat Pump Center, Informative fact sheet, 2002, Hydrocarbons as refrigerants in residential heat pumps and air-conditioners
  12. Calm, J. M. and Domanski, P. A., 2004, R-22 replacement status, ASHRAE Journal, August, pp. 29-39
  13. Jung, D., Song, Y. and Park, B., 2000, Performance of alternative refrigerant mixtures, Int. J. Refrigeration, Vol. 23, No. 6, pp. 466-474 https://doi.org/10.1016/S0140-7007(99)00066-3
  14. Mulroy, W., Kauffeld, M., McLinden, M. O., and Didion, D. A., 1988., Experimental evaluation of two refrigerant mixtures in a bread- board air conditioner, Proc. of Int. Inst. Refrigeration, Purdue Conference on CFCs, Commissions B1, B2, E1 and E2, pp. 27-34
  15. Jang, Y. S., 1997, Performance and heat transfer characteristics of a heat pump system using hydrocarbon refrigerant mixtures, Ph.D. Thesis, Seoul National University, Seoul, Korea
  16. Bodio, E., Chorowski, M. and Wilczek, M., 1993, Working parameters of domestic refrigerators filled with propane-butane mixture, Int. J. Refrigeration, Vol. 16, No. 5, pp. 353-356 https://doi.org/10.1016/0140-7007(93)90008-V
  17. Domanski, P. A., Didion, D. A. and Chi, J., 2003, NIST vapor compression cycle design program, CYCLE-D version 3.0
  18. Maclaine-cross, I. L., and Leonardi., E., 1997, Why hydrocarbons save energy?, Australian AIRAH Journal, Vol. 51, pp. 33-37