Abstract
In 22.9[kV]-y distribution systems, underground cables are provided with multiple-point ground in which each coaxial-neutral line of the distribution cable lines(A, B, C phases) is 3-wire common grounded. In the underground cable distribution systems, circulating current flows in the coaxial-neutral lines and its magnitude amounts to about $40{\sim}50[%]$ load currents, even though loads are balanced. Power loss due to the circulating current consequently reaches to about 76[%] total losses occurred in all conductor lines. This power loss provokes additional temperature rise of the underground cable lines and finally results in 20[%] reduction of the current capacity of the cables. This paper presents a new ground method to overcome such a problem. The proposed method eliminates the circulating current flowing in the coaxial-neutral line effectively. Measurement results confirmed from the practical site-test show validity and effectiveness of this research.
22.9[kV]-y 배전 방식은 지중 케이블로 전력을 공급하고 있으며 선로 운영상 배전케이블 선로의 동심중성선을 케이블 접속 구간마다 3선 일괄 접지하는 다중 접지방식을 채택하고 있다. 그러나 지중 배전 선로에서 각 상의 부하가 평형일 경우에도 동심중성선에는 부하 전류의 약 40[%](전력구)${\sim}$50[%](관로)의 동심중성선 순환 전류가 발생되고 있기 때문에, 순환전류로 인한 손실이 도체 손실의 76[%]에 달한다. 이러한 손실 전력으로 케이블의 내부온도가 상승되어 케이블의 허용전류 용량이 관로의 경우 20[%] 정도 감소하게 된다. 본 논문은 이와 같은 문제점을 해결하기 위하여 새로운 동심중성선 접지방식을 제안하고 있다. 새로운 방법은 동심중성선의 순환전류를 효과적으로 제거하고 있으며, 그 방안을 직접 계통망에서 적용시켜서 실측하여 본 결과, 그 타당성과 유용성을 확인하였다.