불평등 전계에서 $SF_6/CF_4$ 혼합가스의 절연내력과 PD특성

Breakdown Voltage and PD Characteristics of $SF_6/CF_4$ Mixtures in Nonuniform Field

  • 발행 : 2008.04.01

초록

New gas mixtures are now finding applications such as interrupting media for high-voltage circuit breakers. These mixtures consist of a high content of carbon tetrafluoride($CF_4$) added to sulfur hexafluoride($SF_6$). Nowdays $SF_6$ has been established for the use in gas insulated substations due to its high insulation withstand level and good arc quenching capability. At this paper Breakdown characteristics were investigated for $SF_6/CF_4$ mixtures when AC voltage and standard lightning impulse voltage(LI) was applied in a needle-plane electrodes. And partial discharge(PD) experiments were carried out in the test chamber which was made in needle-plane electrode. And ${\Phi}$-Q-N distribution of partial discharge signals was analyzed. The total pressure of the $SF_6/CF_4$ mixtures was varied within the range of 0.1-0.5 Mpa in the test chamber. The breakdown voltage in needle-plane electrode displayed N shape characteristics for increasing the content of $SF_6$ at positive impulse voltage and the PD inception voltage was increased slightly when pressure of $SF_6/CF_4$ Mixtures was increased. Maximum PD inception voltage is showed in 80% SF6/20%$CF_4$.

키워드

참고문헌

  1. V. N. Maller and M. S. Naidu, "Advances in High Voltage Insulation And Arc Interruption in $SF_6$ And Vacuum", Pergamon press, pp.1-20, 1981
  2. Th. Hinterholzer, W. Boeck. "Breakdown in SF6 influenced by Corona-Stabilization" IEEE, Electrical Insulation and Dielectric Phenomena, pp. 413-416, 2000
  3. Y. Qiu, and Y. P. Feng, "Investigation of $SF_6-N_2,\;SF_6-CO_2\;and\;SF_6$-air as substitutes for $SF_6$ insulation", IEEE International Symposium on Electrical Insulation, Vol. 2, p. 766, 1996
  4. 황청호, 박신우, 김남렬, 허창수. " ,평등전계에서 $SF_6/CF_4$ 혼합가스의 AC 절연내력특성, 한국전기전자재료학회지, Vol. 20, No. 4, p. 381, April 2007 https://doi.org/10.4313/JKEM.2007.20.4.381
  5. B. Gravendeel, P. C. T van der Laan and FJ de Hoog, " External discharge currents in inhomogeneous field configurations " J, Phys, D: Appl, Phys, Vol. 21, pp. 437-441, 1988 https://doi.org/10.1088/0022-3727/21/3/010
  6. Andrej Krivda, " Recognition of Discharge- Discrimination and Classification", Delft Univ. Press, pp. 11-25, 1995
  7. 송병두, 하성철, "볼츠만 방정식에 의한 $CF_4$ 분자가스의 전자이동속도특성에 관한 연구", 전기전자재료학회논문지, Vol. 17, No. 11, p. 1254, 2004
  8. 서상현, 유회영, 김상남, 하성철, " $SF_6$ 가스의 전리 및 부착계수에 관한 연구", 조명전기설비학회지 Vol. 10, No. 6, p. 622, 1996
  9. 황청호, 성허경, 허창수. " 불평등 전계에서 $SF_6/CF_4$ 혼 합가스의 SLI, AC 절연내력특성" 대한전기학회논문지, Vol. 57, No, 2, pp. 245 - 251, 2008
  10. G.J.Cliteur, Y.Hayashi, E.Haginomori, K.Suzuki, "Calculation of the uniform breakdown field strength of $SF_6$ Gas", IEEE Transactions on Dielectrics and Electrical Insulation, Vol. 5, No. 6, p. 847, 1998
  11. V.A.Lisovskiy and V. D. Yegorenkov, " Electrondrift velocity determination in $CF_4\;and\;SF_6$ in a strong electric field from breakdown curves of low-pressure RF discharge", Appl. Phys. 32, p. 2647, 1999
  12. J. Berg, E. Kuffel, "Breakdown voltage characteristics of $SF_6\;/\;CF_4$ mixtures in uniform and nonuniform field gaps", Electrical Insulation and Dielectric Phenomena, Conf, pp. 126 - 129, 1995
  13. W. Ziomek, E. Kuffel "Breakdown and Prebreakdown Characteristics of $SF_6\;/\;CF_4$ Mixtures in Nonuniform Electric Field", High Voltage Engineering, Eleventh International Symposium on Conf. Vol 3, pp. 240 - 243, 1999