Single-phase Active Power Filter Based on Rotating Reference Frame Method for Harmonics Compensation

  • Published : 2008.03.01

Abstract

This paper presents a new control method of single-phase active power filter (APF) for the compensation of harmonic current components in nonlinear loads. To facilitate the possibility of complex calculation for harmonic current detection of the single phase, a single-phase system that has two phases was constructed by including an imaginary second-phase giving time delay to the load current. The imaginary phase, which lagged the load current T/4 (Here T is the fundamental cycle) is used in the conventional method. But in this proposed method, the new signal as the second phase is delayed by the filter. Because this control method is applied to a single-phase system, an instantaneous calculation was developed by using the rotating reference frames synchronized to source-frequency rather than by applying instantaneous reactive power theory that uses the conventional fixed reference frames. The control scheme of single-phase APF for the current source with R-L loads is applied to a laboratory prototype to verify the proposed control method.

Keywords

References

  1. Gengyin Li, Chengyong Zhao, Ming Zhou, Guangkai Li and Zhiye Chen, 'A predicted control scheme of single phase active power filter in electric traction systems', 2000, Advances in Power System Control, Operation and Management, APSCOM-00 International Conference, Vol. 1, pp. 101 - 104
  2. S. Serena, Q. Chongming, M. Qiao and Smedley, 'A single-phase active power filter with double-edge integration control', Nov.-Dec. 2001, IECON '01. The 27th Annual Conference of the IEEE, pp. 949 - 953
  3. H. Akagi, Y. Kanazawa and A. Nabae, 'Instantaneous Reactive Power Compensators Comprising Switching Device without Energy Storage Components,' 1984, IEEE Trans. Ind. Applicat., May.-Jun. Vol. IA-20, No. 3, pp. 625-630 https://doi.org/10.1109/TIA.1984.4504460
  4. M. Aredes, J. Hafner and K. Heumann, 'Three-phase four-wire shunt active filter control strategies,' Mar. 1997, IEEE Trans. Power Electr., Vol. 12, No. 2, pp. 311-318 https://doi.org/10.1109/63.558748
  5. Jinjun Liu, Jun Yang and Zhaoan Wang, 'A new approach for single-phase harmonic current detecting and its application in a hybrid active power system', 1999, Industrial Electronics Society, IECON '99 Proceedings, The 25th Annual Conference of the IEEE, Vol. 2, pp. 849 - 854
  6. M. Saitou, N. Matsui, and T. Shimizu, 'A control strategy of single-phase active filter using a novel d-q transformation', Oct. 2003, Industry Applications Conference, 2003. $38^th$ IAS Annual Meeting. Conference Record, Vol. 2, pp. 1222 - 1227
  7. A. Sannino and J. Svensson, 'Static series compensator for voltage sag mitigation supplying nonlinear loads', Jan. 2002, Power Engineering Society Winter Meeting, 2002. IEEE, Vol. 2, pp. 1147 - 1152

Cited by

  1. Fast Detection Algorithm for Voltage Sags and Swells Based on Delta Square Operation for a Single-Phase Inverter System vol.11, pp.1, 2016, https://doi.org/10.5370/JEET.2016.11.1.157
  2. High-power CSI-fed induction motor drive with optimal power distribution based control vol.98, pp.11, 2011, https://doi.org/10.1080/00207217.2011.601445
  3. Cost-Effective APF/UPS System with Seamless Mode Transfer vol.10, pp.1, 2015, https://doi.org/10.5370/JEET.2015.10.1.195