Abstract
There exist 5 wells drilled at the Yecheon hot spring area, the distance between the wells is about $159m{\sim}702.6m$. The safe yield of each well is controlled by interference drawdown between a pumping well and an observation well after pumping test. The well No. 2 and the well No. 5 are the closest, at the distance of 159 m; therefore interference drawdown between two wells was occurred considerably. The drawdown of the well No. 2 (an observation well) was 16.67 m; the drawdown of the well No. 5 (a pumping well) was 17.21 m. The degree of the interference is about 97% and the safe yield decreased from $750m^3/day\;to\;24m^3/day$. Significant interference between two wells is due to the fact that the aquifer has 1.5 dimensions.
예천온천지구에는 5개 온천공이 개발되어 있으며, 온천공들간의 거리는 약 $159.0m{\sim}702.6m$정도이다. 온천조사시 적정양수량 평가에 있어서는 각 공에 대한 적정양수량을 평가한 후 온천공간 수위간섭을 고려하여 적정양수량을 조절하도록 되어있다. 2호공과 5호공의 공간 거리는 약 159 m로서 5개 공중 가장 가깝게 위치하고 있으며, 양수시험시 이들간의 수위간섭 현상도 매우 크게 발생하였다. 5호공에서 3일간 양수시 5호공 자체의 수위강하는 17.21 m 이었으며, 2호공의 수위강하 역시 16.67 m로 두 공간에는 약 0.54 m 정도의 차이만을 보였다. 따라서 온천공간 영향의 정도는 약 97%로 매우 높았으며, 적정양수량도 당초 $750m^3/day$에서 $24m^3/day$로 감하였다. 또한 이와 같이 두 공간에 영향이 심한 원인은 대수층이 1.5차원에 기인한 것으로 해석된다.