Abstract
In recent years. YBCO coated conductor (CC) called as second generation HTS (high temperature superconducting) wire has been developed as a suitable material for resistive superconducting fault current limiter (SFCL). For designing the SFCL. the required length of superconducting wire is inverse proportional to the maximum temperature reached when a fault occurs. Since the required length strongly affects a manufacturing cost, it is the most important parameter to determine the maximum temperature reached. It is necessary to observe the repetitive over-current characteristics of HTS wire. This paper attempts to measure the variation of critical current of YBCO CC after repetitive over-current pulse. No degradation of the critical current of CC sample was observed by applying 100 times over-current pulse which makes temperature above 400 K after 100ms. This study can be useful in designing optimally resistive SFCL employing YBCO CC. The maximum permissible temperature can be set to 400K. so wire length could be reduced by 30% compared in case of 300K-criterion.