Abstract
Six prototype field tests (five 1/8 and one 1/2 scale tests) have been conducted in order to determine the uplift resistance of deep foundation for transmission line structures. Test sites, located in the city of Eumseng in Choongbuk province, are classified as gneiss. These test results reveal failures not along the foundation-rock interface but either along the damaged surrounding rock mass caused by excavation or along the pre-existing rock joint. Test results also show the uplift resistance which is 20 $\sim$ 30% higher than the current design strength of side friction. In addition to fold tests, four concrete core samples between the liner plate and the surrounding rock mass have been obtained from the existing transmission foundations to study the effect of the liner plate which is installed prior to placing concrete. The compressive strength of these concrete core samples shows 63 $\sim$ 72% of the strength at the time of foundation construction. Side frictional resistance based on such less compacted concrete reaches satisfying uplift design strength.
본 논문에서는 송전철탑 심형기초의 주면마찰력을 평가하고자 충북 음성지역의 편마암에 대해 총 6회(1/8규모 5회, 1/2규모 1회) 현장시험을 실시하였다. 시험결과 파괴형태는 기초체와 암반의 마찰파괴가 아닌 굴착으로 인한 손상된 주변암반 및 기존암반의 절리상태에 지배되는 것으로 나타났으며, 주면마찰력 평가결과 기존의 송전철탑 심형기초에 적용하고 있는 값보다 약 20$\sim$30% 증가되는 것을 확인할 수 있었다. 또한 기초타설시 사용되는 라이너플레이트의 영향을 살펴보고자 기존 철탑 기초에 대해 시추조사를 4회 실시하였다. 라이너플레이트 배면콘크리트의 압축강도는 타설시 설계강도의 63$\sim$72%였으며, 주면마찰력의 설계기준치를 만족하는 것으로 나타났다.