Temperature characteristics of condenser and evaporator of Air-conditioner applying variable capacity compressor under cooling condition
가변용량 압축기를 적용한 에어컨의 냉방운전 시 응축 및 증발온도 특성
- Published : 2007.12.31
Abstract
In order to investigate the cooling capacity of an air-conditioner applying a variable capacity compressor and the temperature characteristics on a condenser and an evaporator, the experiment on the operation characteristics of the air-conditioner was performed along a compressor operation ratio and an indoor/outdoor temperatures, under a cooling operation mode. The system characteristics were measured by the psychrometric calorimeter. The cooling capacity increased with decreasing the outdoor temperature and increasing the indoor temperature. Also, it increased with increasing the compressor operation ratio. The temperature of the condenser was more sensitive for the variation of the outdoor temperature and the temperature of the evaporator was more sensitive for the variation of the indoor temperature. The operation characteristics of the cycle used in this present were also analyzed by a pressure-enthalpy chart.
본 연구에서는 냉방운전 시 가변용량방식의 압축기를 적용한 시스템 에어컨의 냉방능력과 증발기 및 응축기의 온도특성을 조사하기 위해 압축기 운전율(10가지)과 실내외 온도(16가지)의 변화에 따른 시스템의 운전특성을 실험적으로 조사하였다. 시스템의 운전특성은 칼로리미터를 이용하여 측정되었다. 냉방능력은 실외온도가 낮아질수록 실내온도가 증가할수록 더 큰 값을 그리고 압축기 운전율이 증가할수록 냉방능력은 선형적으로 증가하였다. 응축온도는 실외온도 변화에 증발온도는 실내온도 변화에 더 민감하였다. 또한 압력-엔탈피선도를 이용하여 사이클의 운전특성을 분석하였다.