Abstract
After various measuring methods and system were investigated, Rogowski colis for the measurement of parameters in current zero region were designed and manufactured. Using the Rogowski coils and a 38kV 40kA VCB (vacuum circuit breaker), at last the post-arc current has been successfully measured firstly. It was found that the Rogowski coils used in this study have good characteristics and propriety to measure the parameters of current zero. We realized that the data processing for evaluating the post-arc current from the experimental results needs much more careful attention than that for building the measuring technique and system. The magnitude of post-arc current and the falling time of it to zero are proportioned to the rate of current di/dt. The magnitude of post-arc currents were around $1{\sim}3A$ to the interruption current of $20{\sim}30kA$ in the model VCB.