A Study on the Analysis of the Lightning Surge Characteristics of Arresters in a 154kV Substation

154kV 변전소에서 피뢰장치의 뇌서지특성 해석

  • 윤창섭 (원광대 대학원 전기공학과) ;
  • 조한구 (원광대 전기전자및정보공학부) ;
  • 이종범 (한국전기연구원)
  • Published : 2006.10.01

Abstract

This paper describes the characteristic evaluation of 154kV lightning arrester developed by domestic technology. To prove the protective ability of lightning arrester developed, various overvoltages were analyzed for A and B arrester were being used now at 154kV air and gas insulation substation, and for arrester developed. The results obtained by the various simulations show that the developed arrester has the effective protective ability and reducing ability of the overvoltage as A and B arrester, nevertheless there are somewhat differences among three kinds of arresters. Accordingly, it is evaluated that the arrester developed by domestic technology secured reliability can be installed actually at 154kV substation. In this paper, EMTP/ATP was used for simulation.

Keywords

References

  1. 한국전기연구소, '뇌서지가 전력계통에 미치는 영향에 관한 연구', 1988. 3
  2. 電力中央硏究所, '??電所耐雷設計ガイドブック', 硏究報告 No.175034, 1976
  3. 한국전기연구원, '발변전용 좌립형 피뢰장치 설계 및 제조기술 개발', 2006. 4
  4. Hideki Motoyama, Hiroji Matsubara, 'Analytical and Experimental Study on Surge Response of Transmission Tower', IEEE Trans. on Power Delivery, Vol. 15, No. 2, 2000. 4 https://doi.org/10.1109/61.853024
  5. 電氣學會技術報告, '發變電所の電サ-ジ解析における各種パラメ-タとその影響' 1989. 6
  6. 우정욱, 심웅보, 'LPATS에 의한 7년간의 한반도 뇌격 특성분포', 대한전기학회 하계학술대회 논문집, 2003
  7. 耐雷技術委員會發變電所分科會, '發變電所侵入雷サ-ジの實用的解析手法とその適用', 1991. 3
  8. 김재관, 정채균, 이종범, 조한구, 서재호, '송전계통 및 변전소 뇌서지 보호방안 연구', 대한전기학회 논문지 54C권 6호, 2005. 6
  9. M. Savic, Z.stojkovic, 'High voltage substation equivalent circuits in the lightning performance estimation,'Generation, Transmission and Distribution', IEE Pro Vol. 141, Issue 2, Mar 1994 https://doi.org/10.1049/ip-gtd:19949760
  10. 電氣學會技術報告, '雷サ-ジ評?高度化のためのモデリング' 1998. 10
  11. 한전 기술연구원, '電力系統過度解析프로그램의 理論 및 活用에 關한 硏究', 最終報告書, 1991