건식이중바닥온돌시스템 개발을 위한 실험적 연구

A Experimental Study for Developing of the Dry Double Floors Hydronic Ondol System

  • 김난행 (한양대학교 대학원 건축공학과) ;
  • 손장열 (한양대학교 건축공학과)
  • 발행 : 2006.06.01

초록

The aim of the research was to evaluate the characteristics of thermal environment and thermal comfort in the Dry Double floors Hydronic Ondol System. Physical indoor thermal environments (the floor surface temperature, the vertical temperature, etc.) and skin temperature have especially been measured. Physical features conditions, sensation, thermal comfort, humidity sensation, comfort of body were investigated for the survey. As a result, (1) During the operation of the boiler (12 hour), the average indoor temperature is appeared to be $21.6^{\circ}C$. The floor surface temperature showed peak value of $31.4{\sim}40.6^{\circ}C$ after 8hours 30minutes after the start-point of the heating. The vertical difference of temperature was turned out to be not uniform. (2) While the skin temperature showed a narrow distribution of temperature in the Dry Double floors Hydronic Ondol system. (3) The response to thermal comfort which people felt was satisfactory, and most of them felt dry during the test.

키워드

참고문헌

  1. 김난행 외(2004), 전통온돌방의 실내온열환경 및 온열감에 관한 연구, 한국주거학회논문집, 제15권 2호
  2. 손장열 외(2004), 이중바닥온돌시스템 개발을 위한 열적특성의 비교 실험연구, 대한건축학회논문집, 제20권 10호
  3. 이무진(1999), 바닥난방의 온열환경 및 열적반응에 관한 연구, 한국주거학회논문집, 제10권 1호
  4. 이주연. 최호선. 이기섭. 허덕. 조관식(2001), 기류를 이용한 실온변동 알고리즘이 인체에 미치는 생리적.심리적 영향에 관한 연구, 한국생활환경학회지, 제8권 제3호
  5. 이철구(2004), 실내 열환경에 대한 최근의 연구동향 고찰, 한국생활환경학회지, 제11권 제2호
  6. 최영식(1992), 기존문헌조사에 의한 바닥난방의 인체영향에 관한 연구, 한국주거학회논문집, 제3권 1호
  7. ASHRAE STANDARD 55-1992, Thennal Environmental Conditions for Human Occupancy
  8. ASHRAE(1997), ASHRAE Handbook Fundamentals, Chapter 8 Thennal Comfort
  9. ISO 7730-1994, Moderate thennal environments
  10. P.O. Fanger(l970), 'Thennal Comfort', McGraw Hili