Study for Field Inspection of Phase-Array Ultrasonic for Electro-fusion Joints of Polyethylene Gas Pipes

폴리에틸렌 가스배관 전기융착부 위상배열초음파검사 현장사례 연구

  • Kil Seong-Hee (Dept. of Gas Safety R&D Center, Korea Gas Safety Corporation) ;
  • Kwon Jeong-Rock (Dept. of Gas Safety R&D Center, Korea Gas Safety Corporation) ;
  • Park Kyo-Shik (Dept. of Gas Safety R&D Center, Korea Gas Safety Corporation)
  • 길성희 (한국가스안전공사 가스안전연구개발원 제품연구실) ;
  • 권정락 (한국가스안전공사 가스안전연구개발원 제품연구실) ;
  • 박교식 (한국가스안전공사 가스안전연구개발원 제품연구실)
  • Published : 2006.06.01

Abstract

We developed the ultrasonic phased array technique for obtaining ultrasonic images of electrofusion joints of polyethylene piping. And we inspected 4 cases at fields with this technique. First case is for the 300 mm diameter polyethylene electrofusion joint by using 3.5 MHz phased array sensor, second is for the 350 mm diameter saddle electrofusion joint, third is for the 400 mm diameter electrofusion joints and the last one is for the 400 mm diameter piping joints which will be used at 300 kPa suppling pressure.

폴리에틸렌(PE) 배관 전기융착부에 대하여 위상배열초음파기술을 이용하여 전기융착부에 대한 비파괴검사를 실시하였다. 사례 1은 직경 300 mm의 PE배관 전기융착부에 대하여 3.5 MHz 배열초음파 센서를 이용하여 건전성 평가를 실시하였으며 사례 2는 직경 350 mm 3개의 새들융착부에 대하여 건전성을 평가하였고 사례 3은 400 mm 전기융착부에 대하여 3.5 MHz 배열초음파 센서를 가지고 비파괴검사를 실시하였다. 그리고 검사한 결과를 절단시험 결과와 비교하였다. 사례 4는 도시가스의 공급압력이 300 kPa인 400 mm PE배관 전기융착부를 탐상하고 그 결과를 살펴보았다.

Keywords