Abstract
Maintaining adequate chlorine residual is crucial in water treatment facilities, Treatment technique, newly promulgated regulation, requires sufficient disinfection in order to control more resistant microorganisms such as Viruses and Giardia lamblia. Each water treatment plant should report various water qualities including chlorine residual and disinfection by-products, thus plenty of data has been generated. Even though statistical analysis using these data are forced to investigate the status and effect of water qualities in water facilities very few researches have been performed in korea. This study performed statistical analysis of chlorine residual during three years in Korean drinking water. The average chlorine residual concentrations were 0.701mg/L, 0.738mg/L, 0.763mg/L in 2002, 2003, 2004, respectively. Monthly variations of chlorine residual was not significant. ANOVA result showed that yearly variance of chlorine residual is different in only less than $5000m^3/day$ of water treatment capacity. The statistical analysis can help government to establish new regulation with scientific basis.