초록
This study conducted to optimize the design and operation of orifice typed distribution channels which were generally constructed to link the rapid mixing process and flocculation/sedimentation basin. To accomplish the goal of this study, programming step method using FORTRAN 90, was applied it to simulate the performance of existing distribution channel in the selected S DWTP (Drinking Water Treatment Plant). The proposed step method program was validated in terms of the feasibility with comparison between the measurement and prediction value in each orifice. From the evaluation results of the current conditions with the design and operation, it was revealed that the existing gradient of the tapered channel is not appropriate. Also, we suggested that in the case of the inlet width being 3.5m, reducing the downstream width by about 0.5m would make more equitable distribution flow in the channel. Consequently, dealing with various conditions of the design and operation with distribution channel, we could conclude that for the parallel typed channel, as the width is wider and the diameter of orifice is smaller, the more equitable distribution occur. In addition, the inlet flowrate and the number of orifice can affect the flow velocity in the channel.