전류변성기 비교 측정 장치의 비오차 및 위상각 오차의 직선성 현장 평가기술

On-Site Evaluation Technique of Linearity for Ratio Error and Phase Angle Error of Current Transformer Comparison Measurement Equipment

  • 발행 : 2006.06.01

초록

A method for evaluation of the linearity of both the ratio error and phase angle error in the current transformer(CT) comparison measurement equipment has been developed by employing the standard resistors with negligible AC-DC resistance difference less than $10^{-5}$. The non-reactive standard resistors for the linearity check of the system are used as the external burden connected with the secondary of CT under test. These burdens consist of nine standard resistors, with the nominal resistance of $0.01{\Omega},\;0.1{\Omega},\;0.2{\Omega},\;0.4{\Omega},\;0.6{\Omega},\;1{\Omega},\;2{\Omega},\;4{\Omega}$, and $10{\Omega}$. For linearity check, the developed method has been applied in the CT comparison measurement equipment belonging to the industry.

키워드

참고문헌

  1. 정재갑, 권성원, 박영태 '전압변성기 비교 측정 장치의 비오차 및 위상각 오차의 직선성 평가기술', 대한전기학회지, 53C권(9호), 470-474(2004)
  2. John D. Ramboz and O. Petersons, 'A Calibration Service for Current Transformers' NIST Special Publication, vol. 250, No. 36, p66(1991)
  3. 정재갑, 권성원, 이상화, 박영태 '전류변성기의 비오차와 위상각 오차의 계산값과 실험값의 차에 의한 측정시스템 유용성 검증기술에 관한 연구', 대한전기학회지, 53C 권(4호). 213-217(2004)
  4. P. J. Betts, 'Calculated Temperature Coefficients of Transformers' National Measurement Laboratory Technical Paper No 4, pp. 1-13(1977)
  5. Tinsley 'Precision Resistance Measurement', Tinsley Precision Instruments 1995
  6. 한국표준협회, '계기용변성기(표준용 및 일반계기용)', KS C 1706, 1982