초록
Partial Discharge (PD) phenomena occurred by different nature of insulating defects has been regarded as a random process by which Phase Resolved Partial Discharge Analysis(PRPDA) has been proposed and then commercially accepted for the diagnosis of the power apparatus since more than three decades. Moreover, for the same purpose, a novel approach based on the Chaotic Analysis(CAPD) has been proposed since 2000, in which Partial Discharge(PD) phenomena is suggested to be considered as a deterministic dynamical process. In this work, for the diagnosis of Gas Insulated Transformer(GITr), four different types of specimen were fabricated as a model of the possible defects that might possibly cause its sudden failures such as turn to turn insulation, inter coil insulation, free moving particle and protrusion. For this purpose, these defects are introduced into the Gas Insulated Transformer(GITr) mock-up and experimental investigations have been carried out in order to analyze the related Partial Discharge(PD) patterns by means of both Phase Resolved Partial Discharge Analysis(PRPDA) and Chaotic Analysis(CAPD) respectively and then their comparisons are made systematically.