Abstract
An experimental study was conducted to investigate seismic behaviour of post-tensioned(PT) exterior slab-column connections used for the purpose to resist gravity loads only. For these, 2/3-scale, two PT post-tensioned exterior connections with two different tendon arrangement patterns and one conventional reinforced concrete(RC) exterior connection was tested under quasi-static, uni-directional reversed cyclic loading. During the lateral testing, gravity forces transferred to the column were kept constant to closely simulate a moment to shear ratio of a real building. One of the objectives of this study was to assess the necessity and/or the quantity of bottom bonded reinforcement needed to resist moment reversal which would occur under significant inelastic deformations of the adjacent lateral force resisting systems. The ACI 318 and 352 provisions for structural integrity were applied to provide the bottom reinforcement passing through the column for the specimens. Prior test results were also collected to conduct comparative studies for some design parameters such as the tendon arrangement pattern, the effect of post-tensioning forces and the use of bottom bonded reinforcement. Consequently, the impact of tendon arrangement on the seismic performance of the PT connection, that is lateral drift capacity and ductility, dissipated energy and failure mechanism, was considerable. Moreover, test results showed that the amount of bottom reinforcement specified by ACI 352. 1R-89 was sufficient for resisting positive moments arising from moment reversal under reversed cyclic loads. Shear strength of the tested specimens was more accurately predicted by the shear strength equation(ACI 318) considering the average compressive stress over the concrete($f_{pc}$) due to post-tensioning forces than that without considering $f_{pc}$.
본 연구의 목적은 중력 하중에 저항하도록 설계된 플랫 플레이트 외부 접합부의 이력 거동을 평가하는 데 있다. 이러한 목적을 위하여 2/3의 크기가 조정된 PT 슬래브-기둥 외부 접합부 2개와 RC 슬래브-기둥 외부 접합부 1개를 대상으로 실험적 연구를 수행하였다. 여기서 각각의 PT 실험체는 서로 다른 강선 배치 형태를 띄고 있다. 중력 하중은 동일하게 설정하였고, 지속적인 정적 하중 하에서 유사 정적 횡하중을 적용하였다. 한편 모든 실험체는 ACI 318-05과 ACI 352.1R-89에 근거하여 기둥 폭 내에 하부 철근을 배근 하였다. 또한 PT 외부 접합부의 이력 거동에 대한 일반적인 결론을 얻기 위하여 기존 연구자들의 실험 결과와 함께 비교하였다. 이번 연구를 통하여 강선의 배치는 PT 접합부의 이력 거동을 결정하는 중요한 변수임을 확인하였다. 즉 횡변형 성능, 에너지 소산 능력, 파괴 메커니즘, 그리고 연성 능력이 강선의 배치에 따라 다르게 나타났다. 또한 ACI 352.1R-89에서 구조적 일체성을 위해 제공된 하부 철근의 양은 모멘트 역전에 의해 발생된 정모멘트를 저항하는데 있어서도 적절하다는 것이 밝혀졌다. 또한 실험체의 전단 강도는 강선의 포스트 텐션에 의한 평균 콘크리트 압축 응력($f_{pc}$)의 효과가 고려된 식이 그렇지 않은 식보다 전단 강도를 정확히 예측하는 것으로 나타났다.