DOI QR코드

DOI QR Code

Topological Locating of Power Quality Event Source

  • Won Dong-Jun (School of Electrical Engineering, INHA University) ;
  • Moon Seung-Il (School of Electrical Engineering and Computer Science, Seoul National University)
  • 발행 : 2006.06.01

초록

This paper proposes a topological locating algorithm to determine the location of the power quality event source. This algorithm makes use of the information on the topology of the monitored network and on the direction of PQ events. As a result, the bus incidence matrix is modified using monitor location and the direction matrix is constructed. With this information, the algorithm determines the suspected locations of the PQ events. To reduce suspicious areas, it utilizes event cause and related equipment. In case of line fault event, it calculates the distance from the monitor to the location of event source. The overall algorithm is applied to the IEEE test feeder and accurately identifies the event source location.

키워드

참고문헌

  1. Mark McGranaghan, 'Trends in Power Quality Monitoring,' IEEE Power Engineering Review, vol. 21, Issue 10, pp. 3-9,21, Oct. 2001
  2. G. T. Heydt, 'Identification of Harmonic Sources by a State Estimation Technique,' IEEE Trans. Power Delivery, vol. 4, no. 1, pp. 569-576, Jan. 1989 https://doi.org/10.1109/61.19248
  3. Astrat Teshome, 'Harmonic Source and Type Identification in a Radial Distribution System,' Conference Record of the 1991 IEEE Industrial Applications Society Annual Meeting, vol. 2, pp. 1605-1609, 1991
  4. Anthony C. Parsons, W. Mack Grady, Edward J. Powers, John C. Soward, 'Rules for Locating the Sources of Capacitor Switching Disturbances,' IEEE Power Engineering Society Summer Meeting, vol. 2, pp. 794-799, 1999
  5. Anthony C. Parsons, W. Mack Grady, Edward J. Powers, John C. Soward, 'A Direction Finder for Power Quality Disturbances Based Upon Disturbance Power and Energy,' IEEE Trans. Power Delively, vol. 15, no. 3, pp. 1081-1086, July 2000
  6. L. Cristaldi, A. Ferrero, S. Salicone, 'A Distributed System for Electric Power Quality Measurement,' IEEE Transactions on Instrumentation and Measurement, vol. 51, no. 4, pp. 776 -781, Aug. 2002 https://doi.org/10.1109/TIM.2002.803300
  7. Ben Byman, Tom Yarborough, Rudolf Schnorr von Carolsfeld, John Van Gorp, 'Using Distributed Power Quality Monitoring for Better Electrical System Management,' IEEE Transactions on Industvy Applications, vol. 36, no. 5, pp. 1481-1485, Sep.-Oct. 2000 https://doi.org/10.1109/28.871298
  8. Glenn W. stagg, Ahmed H. El-Abiad, Computer methods in power systems analysis, New York: Mcgraw-Hill, Inc., 1968
  9. Mark Allen Weiss, Data Structures & Problem Solving using JAVATM, 2nd ed., Addison Wesley, Inc., 2002, pp. 570
  10. Distribution System Analysis Subcommittee Report, Radial Distribution Test Feeders, http://ewh.ieee.org/ soc/pes/dsacom/testfeeders.html

피인용 문헌

  1. Accurate voltage sag-source location technique for power systems using GACp and multivariable regression methods vol.56, 2014, https://doi.org/10.1016/j.ijepes.2013.11.003
  2. Optimal Number and Locations of Power Quality Monitors Considering System Topology vol.23, pp.1, 2008, https://doi.org/10.1109/TPWRD.2007.911126
  3. Development of a network-based power quality diagnosis system vol.77, pp.8, 2007, https://doi.org/10.1016/j.epsr.2006.09.011
  4. Transmission Expansion Planning Using Contingency Criteria vol.22, pp.4, 2007, https://doi.org/10.1109/TPWRS.2007.908478
  5. Analysis of the origin of measured voltage sags in interconnected networks vol.154, 2018, https://doi.org/10.1016/j.epsr.2017.09.008
  6. Locating the source of voltage sags: Full review, introduction of generalized methods and numerical simulations vol.77, 2017, https://doi.org/10.1016/j.rser.2017.04.017