Study on Condensing Pressure Drop of Hydrocarbon Refrigerants

탄화수소계 냉매의 응축 압력강하에 관한 연구

  • 김재돌 (동명대학교 환경설비공학과) ;
  • 최준혁 (부경대학교 대학원 냉동공조공학과) ;
  • 정석권 (부경대학교 기계공학부) ;
  • 윤정인 (부경대학교 기계공학부) ;
  • 이호생 (부경대학교 대학원 냉동공조공학과)
  • Published : 2006.03.01

Abstract

Experimental results for pressure gradient of HCs refrigerants R-290. R-600a. R-1270 and HCFC refrigerant R-22 during condensing inside horizontal double pipe heat exchangers are presented. The test sections which have the tube inner diameter of 10.98mm. and the tube inner diameter of 8mm are used for this investigation. Hydrocarbon refrigerants have higher pressure drop than R-22 in both test sections with the diameters of 12.70mm and 9.52mm. Pressure drop increased with the increase of the mass flux. These results form the investigation can be used in the design of heat transfer exchanger using hydrocarbons as the refrigerant for the air-conditioning systems

Keywords

References

  1. Molina, M. J. and Rowland, F. S., 'Stratospheric Sink for Chlorofluoromethanes: Chlorine Atom Catalyzed Destruction of Ozone', Nature, Vol. 249, pp. 810-814, 1974 https://doi.org/10.1038/249810a0
  2. Kurylo, M. J., 'The Chemistry of Stratosp heric Ozone: Its Response to Natural and Anthropogenic Influences', International Journal of Refrigeration, Vol. 13, pp. 62-72, 1990 https://doi.org/10.1016/0140-7007(90)90003-F
  3. Ebner, T. and Halozan, H., 'Testing the Available Alternative-An Examination of R-134a, R-152a and R-290', IEA HPC Newsletter, Vol. 12, No. 1, Sittard, The Netherlands, 1994
  4. James, R. W. and Missenden, J. F., 'The Use of Propane in Domestic Refrigerators, International Journal of Refrigeration', Vol. 15, No. 2, pp. 95-100, 1992 https://doi.org/10.1016/0140-7007(92)90033-Q
  5. Haraguchi, H., Koyama, S., and Fujii, T., 'Condensation of Refrigerant HFC22, HFC134a and HCFC123 in a Horizontal Smooth Tubes(1st Report, Proposals of Empirical Expression for the Local Friction Pressure Drop', Trans. of the JSME(B Series), Vol. 60, No. 574, pp. 2111-2116, 19944 https://doi.org/10.1299/kikaib.60.2111
  6. Haraguchi, H., Koyama, S., and Fujii, T., 'Condensation of Refrigerant HFC22, HFC134a and HCFC123 in a Horizontal Smooth Tubes(2nd Report, Proposals of Empirical Expression for the Local Friction Pressure Drop', Trans. of the JSME(B Series), Vol. 60, No. 574, pp. 2117-2124, 1994 https://doi.org/10.1299/kikaib.60.2117
  7. Cavallini A., Censi G. , D. Del Col, L. Doretti, G. A. Longo, L. Rossetto, 'Experimental investigation on condensation heat transfer and pressure drop of new HFC refrigerants', International Journal of Refrigeration, Vol. 24, No. 1, pp. 73-87, 2001 https://doi.org/10.1016/S0140-7007(00)00070-0
  8. Mark W. Spatz et. al., 'An eraluation of option for replacing HCFC22 in medium temperature refngeratim system', International Journal of Refngeratim, pp. 475-483
  9. Torikoshi., K., Ebisu., T., 'Heat Transfer Characteristics and Pressure Drop Characteristics of R-134a, R-32 and a Mixture of R-32/R-134a Inside a Horizontal Tube', ASHRAE Transaction Research, Vol. 99(2), pp. 90-96, 1993
  10. Moffat, R. J., 'Using Uncertainty Analysis in the Planning of an Experiment', Journal of Fluid Engineering, 107, pp. 173-182, 1985 https://doi.org/10.1115/1.3242452
  11. Holman, J. P., 'Experimental Methods for Engineering', 5th Ed., Mcgraw Hill, 1989