Abstract
This study describes to analyze variation of carbon dioxide gas concentration by experimental and theoretical method according to the using patterns of ventilation system in a model classroom. Concentration of $CO_2$ gas varied by the occupancy and the ventilation systems are operating or not. More than 850 CMH ventilation system can maintain $CO_2$ gas concentration lower than 1,000 ppm along the class time and can be adopted the government guideline. Theoretical modeling of the concentration was performed at well-mixed ideal condition. Delays of concentration decay were shown at each case compared to actual.