Analysis of Thermal Performance of Ground-Source Heat Pump System

지열 이용 히트펌프 시스템의 열성능 해석

  • Shin, U-Cheul (Dept. of Architectural Engineering, Daejeon University) ;
  • Baek, Nam-Choon (Korea Institute of Energy Research, Solar thermal Research Center) ;
  • Kim, Ook-Joong (Korea Institute of Machinery & Materials, Energy System Research Center) ;
  • Koh, Deuk-Yong (Korea Institute of Machinery & Materials, Energy System Research Center)
  • 신우철 (대전대학교 건축공학과) ;
  • 백남춘 (한국에너지기술연구원 태양열이용센터) ;
  • 김욱중 (한국기계연구원 에너지기계연구센터) ;
  • 고득용 (한국기계연구원 에너지기계연구센터)
  • Published : 2006.06.30

Abstract

The purpose of this study is to present the simulation results and an overview of the performance assessment of the Ground-Source Heat Pump(GSHF) system. The calculation was performed for two design factors: the spacing between boreholes and the depth of the vertical ground heat exchangers. And the simulation was carried out using the thermal simulation code TRNSYS with new model of water to water heat pump developed by this study. As a result, it was anticipated that the yearly mean COPs of heat pump for heating and cooling are about 3.7 and 5.8 respectively and the heat pump can supply 100% of heating and cooling load all the year around.

Keywords

References

  1. J. Lund, B. Sanner, L. Rybach, R. Curtis and G. Hellstrom, Ground-sorce Heat Pumps - A World, Overview, Renewable Enrgy Worlrd, pp. 218-227, 2003
  2. J. Warnelov, Ground-Coupled Heat Pump Market and Prospects in Europe, 7th IEA Heat Pump Conference, Beijing, 2002
  3. University if Wisconsin-Maidison, TRNSYS 14.2 Reference manual, 1996
  4. 이세균, 김대기, 우정선, 박상일,'1차원 모델에 의한 지중열교환기의 열거동 해석', 한국태양에너지학회 논문집, Vol.25, No. 1, pp. 97-104, 2005
  5. A. Murugappan, Implementing Ground Source Heat Pump and Ground Loop Heat Exchanger Models in the Energyplus Simulation Environment, M.S. These, Oklahoma state University, 2001