Abstract
In this paper, we developed HPF (high pass filter) consists of lumped LC components to decrease the noises that are detected in PD (partial discharge) measuring test, and adapted it to field test. We tested it under laboratory circumstances like the fields, and measured the phase change properties of detected signal in UHF sensor with Lemke Probe and oscilloscope (TDS-3054, Tektronix). As a result, we obtained available data showing the decrease of noises in the experiments with the developed HPF from the joint box of 22.9kV distribution line. The result can be adapted to prevent the degeneration of the XLPE power cable, and to observe and diagnosis the underground power transmission cable at the ultra-high voltage.