Modal Identification and Seismic Performance Evaluation of 154kV Transformer Porcelain Bushing by Vibration Test

진동시험에 의한 154kV 변압기 부싱의 동특성 분석 및 내진성능 평가

  • 조양희 (인천대학교 토목환경시스템공학과) ;
  • 조성국 (인천대학교 공학기술연구소)
  • Published : 2006.10.30

Abstract

The power supply system is one of the most important infrafacilities which should maintain their inherent function during and after earthquakes. This study was performed to analyze dynamic characteristics and seismic performance of Korean typical 154kV transformer porcelain bushing. For the purpose of this study, actual 154kV porcelain bushings were selected and tested on the shaking table. The vibration tests consist of modal identification tests, seismic performance tests, and fragility tests. The sine sweep waves, artificial earthquake waves, and continuous resonant sine waves were used as shaking table motions. This paper describes the test specimens, shaking facilities, and test methods. Natural frequencies and damping ratios of the bushing have been evaluated from the experimental data. The failure mode and the performance level of the Korean transformer bushing have been first identified in this study.

지진과 같은 재난이 발생하였을 때에도 전력설비는 그 본래의 기능을 상실하지 않고 구조적인 안정성을 유지해야 하는 핵심 산업시설물이다. 이 연구는 가장 대표적인 전력설비인 154kV 변압기에 부착된 애자형 부싱의 진동특성과 내진성능을 분석하였다. 연구의 목적에 따라 국내에서 운용하던 실제 154kV 변압기 부싱을 대상으로 30tonf 용량의 진동대를 이용하여 진동시험이 실시되었다. 진동시험은 동특성분석시험과 내진성능시험 그리고 파괴한도시험으로 구분하고, 각각의 시험에는 정현소인파, 인공지진파 그리고 연속공진정현파를 진동대운동으로 입력하였다. 이 논문에는 시험에 사용된 시편과 진동설비의 특성 그리고, 시험 방법 및 종류를 설명하고, 시험 결과 얻어진 계측자료의 특성에 대하여 논의한다. 이 연구를 통하여 국내에서 운용중인 154kV 변압기 부싱은 그 고유진동수가 20Hz 이상인 고진동수 설비이며, 감쇠비는 4%미만인 것으로 분석되었다. 또한, 특별한 경우를 제외하고, 변압기 부싱은 국내의 설계기준지진에 대하여 충분한 내진안전성을 보유하고 있으며, 강한 공진운동에 의해 예상되는 부싱의 최초 파괴모드는 하단 개스킷의 파손인 것으로 밝혀졌다.

Keywords

References

  1. 전력연구원, '내진설계기준 설정에 따른 송변전설비의 안전도 평가', 최종보고서, 산업자원부, 20004
  2. IEEE, IEEE Recommended Practice for Seismic Design of Substations, IEEE Std 693-1997, Institute of Electrical and Electronics Engineers, Inc., 1997
  3. 日本電氣協會,費電所等におけゐ電氣設備の冊震設計指針, JEAG 5003, 1999
  4. 전력 연구원, '송. 변전설비 내진설계기준 설정 연구', Technical Report, 01전력연-단601, 한국전력공사 전력연구원, 2001
  5. 전력연구원, 송변전설비 내진설계 실무지침서(안), 한국전력공사 전력연구원, 2003
  6. Gilani, A. S., Chavez, J. W., Fenves, G. L. and Whittaker, A. S., 'Seismic Evaluation of 196kV Porcelain Transformer Bushings,' PEER-1998/02, Pacific Earthquake Engineering Center, University of California, Berkeley, 1999
  7. Kiureghian, A. D., Sackman, J. L. and Hong, K. J., 'Interaction in Interconnected Electrical Substation Equipment Subjected to Earthquake Ground Motions,' PEER-1999/01, Pacific Earthquake Engineering Center, University of California, Berkeley, 1999
  8. Gilani, A. S., Whittaker, A. S., Fenves, G. L. and Fujisaki E., 'Seismic Evaluation of 550kV Porcelain Transformer Bushings,' PEER-1999/05, Pacific Earthquake Engineering Research Center, University of California, Berkeley, 1999
  9. 한국전기연구소, 전기재료편람, 제3장 절연재료, 데이컴인터내셔널. 1990
  10. Bendat, J. S. and Piersol, A. G., Random Data - Analysis and Measurement Procedures, 3rd Ed., John Wiely & Sons, Inc., 2000
  11. Littl, J. N. and Shure, L., Signal Processing Toolbox User's Guide for Use with MATLAB, The Math Works, Inc., 1993
  12. The STAR SystemTM, User Manual, Spectral Dynamics, Inc., 1996

Cited by

  1. Seismic Performance Evaluation of 500 kV EBA vol.25, pp.7, 2015, https://doi.org/10.5050/KSNVE.2015.25.7.496
  2. The Experimental Study on Seismic Capacity of 154 kV & 345 kV Main Transformer Bushings vol.22, pp.2, 2018, https://doi.org/10.5000/EESK.2018.22.2.087