순간전압강하에 의한 단상 민감부하 및 삼상 유도전동기의 외란 민감도에 관한 연구

A Study on the Susceptibility of Single-phase Sensitive Loads and the Three-phase Induction Motor by Voltage Sag

  • 윤상윤 (LS산전 전력연구소) ;
  • 문종필 (기초전력연구원 전력시스템연구실) ;
  • 김재철 (숭실대 공대 전기공학부) ;
  • 이희태 (숭실대 공대 전기공학부)
  • 발행 : 2006.01.01

초록

In this paper we explore the susceptibility of common sensitive loads by voltage sags of power distribution systems. The experimental approach was used for obtaining the susceptibility of single-phase loads and the three-phase induction motor. The experimental result of single-phase loads was transformed to the ITIC(Information of Technology Industry Council) format and used for evaluating the adverse impacts of a individual and repetitive sags using the performance contour of the foreign standard data. In order to assess the impact of voltage sags on three-phase induction motor, also, the experiment was peformed. The experiment was focused on the current, torque, and speed loss of the motor during a voltage sag. For comparing the impacts of individual and repetitive voltage sags, the variations of motor torque is focused among the experimental results. The sensitive curves of instantaneous current peak are used to describe the susceptibility of three-phase induction motor and 진so it were used for the quantitative analysis of the impact of three-phase induction motor due to voltage sags. Through the results of experiment, we verified that some types loads have more severe impact at repetitive voltage sags than individual ones and proposed method can be effectively used to evaluate the actual impact of voltage sags.

키워드

참고문헌

  1. IEEE recommended practice for monitoring electric power quality, IEEE Std. 1159,1995
  2. IEEE guide for service to equipment sensitive to momentary voltage disturbances, IEEE Std. 1250,1995
  3. Electromagnetic compatibility (EMC), Part 2: Environment, Section 2: Voltage dips,short interruptions and statistical measurement results, IEC61000-2-8
  4. C. Becker et al., 'Proposed chapter 9 for predicting voltage sags (dip) in revision to IEEE Std 493, the Gold Book,' IEEE Trans. on Ind. Appl., vol. 30, no .3, pp. 805-821, May/Jun. 1994 https://doi.org/10.1109/28.293731
  5. Y. Sekine, T. Yamamoto, S. Mori, N. Saito, and H. Kurokawa, 'Present state momentary voltage dip interferences and the countermeasures in Japan,' Int. Conf. on Large Electric Networks (CIGRE), 34th Session, Sep. 1992
  6. J. Lamoree, D. Mueller, P. Vinett, W. Jones, and M. Samotyj, 'Voltage sag analysis case studies,' IEEE Trans. on Ind. Appl., vol. 30, no. 4, pp. 1083-1089, Jul./Aug. 1994 https://doi.org/10.1109/28.297926
  7. L. E. Conrad and Math H. J. Bollen, 'Voltage sag coordination for reliable plant operation,' IEEE Trans. on Ind. Appl., vol. 33, no. 6, pp. 1459-1464, Nov./Dec. 1997 https://doi.org/10.1109/28.649956
  8. R. C. Dugan, D. L. Brooks, M. Waclawiak, and A. Sundaram, 'Indices for assessing utility distribution system RMS variation performance,' IEEE Trans. on PWRD, vol. 13, no. 1, pp. 254-259, Jan. 1998 https://doi.org/10.1109/61.660886
  9. G.-J Lee, M. M. Albu, G. T. Heydt, 'A power Quality index based on equipment sensitive, cost, and network vulnerability', IEEE Trans. on PWRD, vol. 19, no. 3, pp. 1504-1510, Jul. 2004 https://doi.org/10.1109/TPWRD.2004.829124
  10. J. C. Gomez, M. M. Morcos, C. A. Reineri, and G. N. Campetelli, 'Behavior of induction motor due to voltage sags and short interruptions,' IEEE Trans. on PWRD, vol. 17, no. 2, Apr. 2002 https://doi.org/10.1109/61.997914
  11. L. Guasch, F. Corcoles, J. Pedra, 'Effects of symmetrical and unsymmetrical voltage sags on induction machines', IEEE Trans. on PWRD, vol. 19, no. 2, Apr. 2004 https://doi.org/10.1109/TPWRD.2004.825258
  12. Math H. J. Bollen, Understanding power Quality problems-voltage sags and interruptions, New York: IEEE Press, 2000
  13. IEEE recommended practice for evaluating electric power system compatibility with electronic process equipment, IEEE Std. 1346, 1998
  14. J. F. Moon, J. C. Kim, S. Y. Yun, B. S. Kang, 'Quantitative Evaluation of the Impact of Low-Voltage Loads Due to the Successive Voltage Sags', Trans. on KIEE, vol. 53A, no. 12, Dec. 2004
  15. J. C. Das, 'Effects of momentary voltage dips on the operation of induction and synchronous motors', IEEE Trans. on Ind. Appl., vol. 26, no. 4, July/August, 1990 https://doi.org/10.1109/28.55998