The Adequacy Analysis for Installation of High Speed Grounding Switches on the Korean 765kV Single Transmission Line

  • Published : 2006.12.01

Abstract

This paper analyzes arc phenomena including the secondary arc's elongation in the Korean 765kV single transmission line (79km) between Sin-Ansung S/S and Sin-Gapyeong S/S, which will be installed in Korea in June 2006. In particular, both frequency independent and frequency dependent line models are compared to make our final decisions. As well, the significant simulation results are investigated by the EMTP program. As a result, there is no need of HSGS in the Korean 765kV single transmission line from both a practical and an economical point of view.

Keywords

References

  1. Korea Electric Power Corporation (KEPCO), 'A Study on the Protective Relaying Scheme for 765kV Power System', pp. 110-115,242-259, 1994
  2. C. H. Kim and S. P. Ahn, 'The simulation of high speed grounding switches for the rapid secondary arc extinction on 765 kV transmission lines,' in Proc. of the Int'l Conf on Power Systems Transients, Hungary, pp. 173-178, June 1999
  3. Korea Electric Power Corporation (KEPCO), 'Report for 765kV facilities', Jan. 2004
  4. A.T. Johns, R.K. Aggarwal and Y.H. Song, 'Improved Techniques for Modeling Fault Arcs on Faulted EHV Transmission Systems', lEE Proc-Gener. Transm. Distrib., vol. 141, no. 2, pp. 148-154, March 1994 https://doi.org/10.1049/ip-gtd:19949869
  5. S. Goldberg, William F. Horton and D. Tziouvaras, 'A Computer Model of the Secondary Arc in Single Phase Operation of Transmission Lines', IEEE Trans. Power Delivery, vol. 4, no. 1, pp. 586-594, Jan. 1989 https://doi.org/10.1109/59.193833
  6. M. Kizilcay, L. Prikler, G. Ban and P. Handl, 'Improved Secondary Arc Models based on Identification of Arc Parameters from Staged Fault Test Records', in Proc. 14th Power Systems Computation Conf., Session 24-Paper 3, June 2002
  7. I. M. Dudurych, T.J. Gallagher, E. Rosolowski, 'Arc Effect on Single-Phase Reclosing Time of a UHV Power Transmission Line', IEEE Trans. Power Delivery, vol. 19, no. 2, pp. 854-860, April 2004 https://doi.org/10.1109/TPWRD.2004.824404
  8. S.P. Ahn, C.H. Kim, R.K. Aggarwal and A.T. Johns, 'An alternative approach to adaptive single pole autoreclosing in high voltage transmission systems based on variable dead time control', IEEE Trans. Power Systems, vol. 16, no. 4, pp. 676-686, Oct. 2001
  9. C.H. Kim, S.P. Ahn, 'A Study on the Arc Modeling in Transmission Lines using EMTP', in Proc. of the Int'l Power Engineering Coni, Singapore, vol. I, pp. 52-57, May 1999
  10. Laurent Dube, Users Guide to MODELS in ATP (New Version), April, 1996
  11. Canadian/American EMTP User Group, ATP Rule Book, 1995

Cited by

  1. Analysis of the Neutral Current for Two-Step-Type Poles in Distribution Lines vol.24, pp.3, 2009, https://doi.org/10.1109/TPWRD.2009.2021031
  2. Superconducting Fault Current Limiter Application for Reduction of the Transformer Inrush Current: A Decision Scheme of the Optimal Insertion Resistance vol.20, pp.4, 2010, https://doi.org/10.1109/TASC.2010.2048214