낙뢰측정 네트워크(KLDNet)를 위한 감지기 사이트서베이와 낙뢰 감지율 검토

A study on the Site Survey and Detection Efficiency for Kepco Lightning Detection and Information Network

  • 발행 : 2006.11.01

초록

Lightning induced faults accounts for more than 66% at the transmission lines of KEPCO. The lightning causes damages to power system equipments including transmission line, the blackout of electricity and the electro-magnetic interference. Because of this reason, we need the real time lightning information for the optimal operation of power system. And, it is required to obtain and accumulate the lightning current parameters for the insulation design. In 2005, KEPRI constructed a lightning detection network, the KLDNet (i.e. Kepco Lightning Detection & Information System) and launched a lightning information service for KEPCO customers. It is intended to provide data service on the operation of transmission lines and collect lightning-related data, which is the most important factor regulating power system design and operation. The new system will replace LPATS, the old detection system, which has been operating since 1995 and is rapidly failing in terms of both detection performance and location accuracy. The purpose of this paper is to explain the work performed and the results of that work in performing a site survey of several locations. The purpose of the site survey is to find locations acceptable for the installation of a lightning location receiver in support of a Lightning detection system(LDS). A restriction was placed on the surveyed locations, as they must belong to the Korea Electric Power Company. This requirement was made to facilitate the communication needs of the LDS network. Total of 15 sites were evaluated as possible LDS sensor sites. Some of the sites were rejected for physical reasons and therefore no electrical testing was performed. Of the 15 sites, total of 10 sites were considered acceptable and 5 sites were rejected for various reason. In this paper, we would like to explain the site survey and detection efficiency for LDS.

키워드

참고문헌

  1. 심응보, 우정욱, 강연욱, 곽주식, 권동진, '절연설계 신뢰도 향상을 위한 뇌격전류 직접측정 설비 구축에 관한 연구', 2005. 11
  2. Takatoshi Shindo, 'Lightning location systems in Japan and a lightning frequency map using the data obtained by them', 10th ISH, 1987. 8
  3. CRIEPI, 'Guide to Lightning Protection Design of Power Stations, Substations and Underground Transmission Lines', T40, pp. 31-53, 1995. 7
  4. 곽주식, 우정욱, 추진부, 이복희, 장성익, 문재덕, 'The Site Survey Results for New Lightning Detection System of KEPCO', Korea-Japan Symposium Joint Symposium on electrical Discharge and High Voltage Engineering, 2005
  5. 우정욱, 곽주식, 강연욱, 김현주, The Introduction about New KLDNet and the Statistical Distribution of Lightning Parameters in Korea', International Lightning Detection Conference, 2006
  6. 'KEPRI Site Survey Final Report', TOA Systems Inc., May, 2005
  7. KEPCO, 'A Research For Construction of Lightning Position and Tracking System and for Power System Application (Final Report)', pp. 55-90, 1995. 6