22.9kV 폐쇄 배전반내의 사고모델을 통한 실험적 검증

Experimental Verification According to an Accident Model in a Metal-Clad Switchgear at 22.9kV

  • 발행 : 2006.06.01

초록

This paper describes the accident analysis by modelling the current transformer mounting in a metal-clad switchgear at 22.9kV. In analyzing the accident, the reconstruction at the current transformer mounting(VCB connecting guide) has to be taken into account. The accident was modelled as a 3-phase ground fault occurring between the end plate of 22.9kV lines and the safety shutter at the current transformer mounting of the VCB inside the metal clad switchgear. Since the outside maintenance of the metal clad switchgear is restricted by the enclosed compartments, Its circumference has to be kept clean. Through the reconstruction results, it was confirmed that the fault of the enclosed switchboard could be reduced when the shutter made of Fe material was chanted into an insulation.

키워드

참고문헌

  1. 전력정보센터. '주요전력지표', http://www.epic.or.kr/ EPIC/jsp/PIT/EIC_PIT_STD.jsp, 2006
  2. 한국전기안전공사, '전기재해통계분석', 14호, 한국전기안전공사, pp.67-74, 2005
  3. 이덕출, 정성계, '고전압공학', 문운당, pp.39-108, 1991
  4. 송길목, 최충석, 노영수, 곽희로, '트래킹에 의해 열화된 페놀수지의 탄화특성', Trans. KIEE. Vol. 53C, No.1, pp.1-7, JAN. 2004
  5. Chung-Seog Choi, Kil-Mok Shang, Hyang-Kon Kim, Dong-Oak Kim, Dong-Woo Kim, 'The Analysis of Dendrite Structure of Electric Wire Melted by Fusing Current'. 2003J-K Joint Symp. on ED&HVE. pp.145-148. 2003
  6. John D. DeHaan, 'Kirk's Fire Investigation', 5th edition, Prentice Hall, pp.305, 2002
  7. Kil-Mok Shong, Hyang-Kon Kim, Chung-Seog Choi and Hee-Ro Kwak, 'A Study on the Electrical Fire Analysis of PVC lnsulateds Flexible Cord by Over-Current', KIEE 2003spring conference, pp.131-133, 2003
  8. Babrauskas, V., 'Fires due to Electric Arcing: Can 'Cause' Beads Be Distinguished from 'Victim' Beads by Physical or Chemical Testing?', Fire and Materials, pp.189-201, 2003
  9. 전기공사협회, '특별고압가공전선과 지지물 등 사이의 이격거리', 기술기준 제122조, pp.80, 2003