Abstract
The purpose of this paper is to judge the damage cause of instrument transformer(MOF; Metering Out Fit) installed in 22.9kV power receiving system. In the three-dimensional analysis of the restored MOF, the damage pattern progressed from inside to outside, there was no damaged part in the upside. The resistance of the carbonized middle part is roughly $100\kappa\Omega$ and the exothermic temperature at inside is presumed as about $300\~800^{\circ}C$ in the result of metallurgical structure analysis. The structure and the composition rate on metal surface by SEM is similar. In the result of FT-IR analysis, we can observe the absorbtion peak at $1500cm^{-1}\;and\;1730 cm^{-1}$ is small. The high exothermic peak showed at the center part of the coil in the result of DTA.
본 논문은 22.9kV 수전설비에 설치된 계기용변성기의 소손원인을 판정하는데 있다. 복원된 MOF의 입체적 분석에서 사고는 내부에서 외부로 진행되었으며, 상부는 소손이 없었다. 탄화 중심부의 저항은 약 $100\kappa\Omega$이며, 금속조직 분석결과 내부의 발열 온도는 $300\~800^{\circ}C$ 정도로 추정된다. 금속표면의 2차 전자 이미지 분석에서 구조 및 조성비는 유사했다. 적외선 흡광스팩트럼(FT-IR) 분석에서 $1500cm^{-1}$과 $1730cm^{-1}$에서 흡광피크가 작아진 것을 알 수 있다. 열분석(DTA)에서 권선의 중심부에서 연적 피로가 큰 것으로 나타났다.