슬래브축열 공조시스템의 축열성능에 관한 실험적 연구

An Experimental Study on Thermal Storage Performance of an Air Conditioning System with Slab Thermal Storage

  • 정재훈 (세종대학교 세종-록히드마틴 우주항공연구소) ;
  • 신영기 (세종대학교 기계공학과)
  • Jung Jae-Hoon (Sejong-Lockheed Martin Aerospace Research Center, Sejong University) ;
  • Shin Young-Gy (Department of Mechanical Engineering, Sejong University)
  • 발행 : 2005.05.01

초록

This paper investigates the thermal storage performance of the office building which has adopted an air conditioning system with its slab structure as a regenerator. Four cases of the thermal storage performance experiment were conducted. Room air temperatures, floor slab temperatures, temperatures around the air conditioning unit were logged and analyzed. The load handling capacity of the air conditioning unit and the amount of heat stored in the slab were decided from those experiments. Several efficiencies were investigated to evaluate the performance of the thermal storage. The results concluded that the slab as a regenerator is very effective in cutting down peak loads of the office building.

키워드

참고문헌

  1. Ruud, M. D., Mitchell, J. W. and Klein, S. A, 1990, Use of building thermal mass to offset cooling loads, ASHRAE Transactions, Vol. 96, No.2, pp. 820-829
  2. Snyder, M. E. and Newell, T. A., 1990, Cooling cost minimization using building mass for thermal storage, ASHRAE Transactions, Vol. 96, No.2, pp.830-838
  3. Roh, H. W. and Udagawa, M. H., 2001, Simulation study on the performance of a fabric heat storage system, Transactions of AIJ, No. 544, pp.31-38
  4. Lim, J. H., Lee, S. H., Kim, S. H., Chung, K. S. and Yee, J. J., 2002, A study on the potentiality for the thermal storage of effect with air-conditioning system, Proceedings of the SAREK 2002 Winter Annual Conference, pp.569-574
  5. Jung, J. H., 2004, Fundamental study into optimized control for air-conditioning system with floor thermal storage, Ph.D. thesis, University of Kyoto, Kyoto, Japan