전압변성기 비교기를 이용한 부담의 현장교정 기술

On-Site Calibration Technology of Burden using Voltage Transformer Comparator

  • 발행 : 2005.11.01

초록

Both ratio error and phase angle error in voltage transformer(VT) depend on values of VT burden used. Thus, precise measurement of burden is very important for the evaluation of VT. A method of evaluation for VT burden has been developed by employing the portable decade resistor, with AC-DC resistance difference less than 10-3. The burden value(value and power factor) can be obtained by conductance and susceptance, obtained by measuring the change of ratio error and phase angle error caused by the resistance change of decade resistor. The burden value and power factor obtained by the method are consistent with those obtained using power analyzer within corresponding uncertainties.

키워드

참고문헌

  1. J. L. Settles, W. R. Farber, and E. E. Connor, 'The analytical and graphical determination of complete potential transformer characteristics' IEEE Trans. Power Apparatus and Systems, vol. 79, No. 51, pp. 1213-1218, 1961
  2. William E. Anderson 'A Calibration Service for Voltage Transfomers and High-Voltage Capacitors' NBS Measurement Services Special Publication 250-33, 1988
  3. 정재갑, 권성원, 김규태, 김명수, 외부부담이 전압변성기의 비오차와 위상각오차에 미치는 영향에 대한 연구', 대한전기학회지, vol.53C, No.3, pp.137-142, 2004
  4. 한국표준협회, '계기용변성기(표준용 및 일반계기용)', KS C 1706, 1982